 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND PER NFPA 1 - FLORIDA
 EDITION.
  
 PROVIDE A CIVIL ENGINEERING PLAN SHOWING UNDERGROUND
 UTILITIES, CONNECTIONS, FIRE HYDRANTS, PIPE SIZES ETC.
  
 PROVIDE A LIFE SAFETY PLAN (WITH FURNITURE) SHOWING
 OCCUPANT LOADS, TRAVEL DISTANCES TO EXITS, EXIT SIGNS,
 FIRE EXTINGUISHERS, FIRE-RATED WALLS, ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 REFLECTED CEILING PLANS DO NOT INDICATE CEILING
 ELEVATIONS.
  
 STAIR DOORS DO NOT HAVE A FIRE-RATING ACCORDING THE
 DOOR SCHEDULE ON SHEET A-71.
  
 EVERY FLOOR SERVED BY THE ELEVATOR SHALL HAVE AN
 ELEVATOR LOBBY WITH A ONE-HOUR FIRE RATING PER SECTION
 7.2.13.3 OF NFPA 101 - FLORIDA EDITION. ALSO, ELEVATORS
 SHALL NOT OPEN TO AN EXIT PER SECTION 9.4.7 OF NFPA 101
 - FLORIDA EDITION.
  
 SHEET A1-1: PROVIDE ADDITIONAL INFORMATION FOR EXISTING
 METAL CATWALK AND STAIR THAT IS TO REMAIN. INDICATE
 STAIR DISCHARGE LOCATION.
  
 SHEET A-6: GRAND STAIR #103 IS SERVING AS AN EXIT. ALL
 INSIDE STAIRS SERVING AS AN EXIT OR EXIT COMPONENT
 SHALL BE ENCLOSED PER SECTION 7.2.2.5.1.1 OF NFPA 101 -
 FLORIDA EDITION.
  
 SHEET A-6: TICKET RAMP APPEARS TO ONLY HAVE ONE
 HANDRAIL.
  
 SHEET A-7: THE PLAN IS DESIGNATED AS A MEZZANINE BUT
 DOES NOT MEET THE DEFINITION OF MEZZANINE AS PROVIDED
 IN THE FLORIDA BUILDING CODE. THIS LEVEL IS FUNCTIONING
 AS A FLOOR AND NEEDS TO HAVE OPENINGS PROTECTED.
  
 SHEET A-8: THE DOOR SWING OF #322 OBSTRUCTS ACCESS TO
 EXIT STAIR #2.
  
 SHEET A-8: SOME ROOMS REQUIRE TRAVEL THROUGH ANOTHER
 ROOM TO REACH AN EXIT. THESE DOORS CANNOT BE SUBJECT TO
 LOCKING AND PROHIBIT EGRESS.
  
 SHEET A-8: EXTERIOR STAIRS SHALL BE SEPARATED AND HAVE
 PROTECTED OPENINGS PER SECTION 7.2.2.6 OF NFPA 101 -
 FLORIDA EDITION.
  
 SHEET E2-3: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES FOR VOICE EVACUATION SYSTEM. MOST
 NOTIFICATION APPLIANCES ARE SHOWN AS HORN/STROBES.
  
 SHEET E2-3: PROVIDE NOTIFICATION APPLIANCE IN CORRIDOR
 #116.
  
 SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE
 CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE
 HYDRANT LOCATION IN RELATION TO FDC, ETC.
  
 SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, PLANS SHALL INDICATE THE HAZARD
 CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW
 TEST DATA.
  
 NOTE: A DRAWING INDEX WOULD HELP EXPLAIN THE GAP IN
 DRAWING NUMBER SEQUENCE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  