| Plan Review Notes For Permit 11050596 |
| Permit Number |
11050596 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-01 15:39:28 | PROVIDE SPECIFICATIONS FOR THE NEW ELECTRICAL SERVICE | | | EQUIPMENT SHOWING THE EQUIPMENT SELECTED IS CAPABLE OF | | | INTERRUPTING THE AVAILABLE FAULT CURRENT. NEC 110.9, | | | 110.10 | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT. NEC 110.26, | | | 240.24, 408.17 | | | PROVIDE SPECIFICATIONS AND LISTING FROM AN APPROVED | | | TESTING AGENCY FOR THE CUSTOM LIGHTING FIXTURES. NEC | | | 110.3 | | | VERIFY ALL CUSTOM SOUND AND LIGHT SYSTEMS ARE LISTED BY | | | AN APPROVED TESTING AGENCY. NEC 110.3 | | | PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES | | | AND LIGHTING ARRAYS RATED AT MORE THAN 50 POUNDS. NEC | | | 410.36, 314.27 | | | A SEPARATE PLAN AND ELECTRICAL PERMIT IS REQUIRED FOR | | | THE FIRE ALARM SYSTEM. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|