Plan Review Notes
Plan Review Notes For Permit 11050596
Permit Number 11050596
Review Stop B
Sequence Number 1
Notes
Date Text
2011-05-31 15:04:50 
 BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE PLANS OF THE EXISTING SPACE
 INDICATING WHERE THE STAIRWELLS AND EXISTING EXIT
 LOCATIONS. IT APPEARS THE MEZZANINE IS A NEW LEVEL?
 106.1.2 ADDITIONAL INFORMATION REQUIRED. 2007/09 FL
 EXST BLDG CODE 701.3 NEW WORK.
  
 2) WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, IS
 THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT REFERENCE
 THE FLORIDA EXISTING BUILDING CODE AND TO WHICH TYPE OF
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO? FL EXST
 BLDG CODE 101.5 (.1-.3).
  
 3A) SHEET A-1.0 THE BUILDING & CODE INFORMATION
 INDICATES THIS BUILDING TYPE UNDER THE 1997 UBC AS A
 TYPE II-B NON-COMBUSTIBLE/ NONRATED. PLEASE REFER TO
 THE 2007 FBC-B FOR BUILDING TYPE, NOTE THE 2007FBC-B
 603.1.3 REQUIRES ALL ROOF CONSTRUCTION GIRDERS, JOIST,
 TRUSSES AND DECKING ARE TO BE FIRE RETARDANT TREATED
 WOOD. SHEET S-5 INDICATES THE EXISTING 2X6 ROOF
 FRAMING, IS THE EXISTING STRUCTURE TRULY A BUILDING
 TYPE II-B? PLEASE NOTE THE NEW FRAMING MEMBERS LOCATED
 ON SHEET S-5 DO NOT INDICATE THE USE OF FIRE RETARDANT
 TREATED WOOD.
  
 3B) THE BUILDING & CODE INFORMATION FOUND ON SHEET A-1
 DOES NOT INDICATE IF THIS IS A FIRE SPRINKLERED
 BUILDING? 2007/09 FBC-B 106.3.5.1.1. MINIMUM PLAN
 REVIEW CRITERIA.
  
 4A) PLEASE PROVIDE A LIFE SAFETY PLAN W/ FURNISHINGS
 OCCUPANT LOADS & EGRESS CAPACITIES. 2007/09 FBC-B
 106.3.5.1.1(6).
  
 4B) PLEASE PROVIDE COMMON PATH OF TRAVEL FOR THE FIRST
 FLOOR SEE LIMITATIONS 1014.3 FOR THE FIRST FLOOR AS
 WELL AS THE MEZZANINE LEVEL AND THE SECOND FLOOR.
 REVIEW SECTION 505.3 FOR THE MEZZANINE MAXIMUM TRAVEL
 DISTANCE INCLUDES THE DISTANCE TRAVELED ON THE STAIRWAY
 MEASURED IN THE PLANE OF THE TREAD NOSING.
  
 4C) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 OCCUPANCY SEPARATION IN CONJUNCTION TO THE OPEN AIR
 STAIR BETWEEN THE MEZZANINE LEVEL AND THE 2ND FLOOR
 LEVEL?
 2007 FBC-B TABLE 508.3.3.
  
 4D) THE SECOND FLOOR FRONT STAIRWAY IS IN THE SAME
 STAIRWELL AS THE ELEVATOR. 2007 FBC-B 3002.7 COMMON
 ENCLOSURE WITH STAIRWAY. ELEVATORS SHALL NOT BE IN A
 COMMON SHAFT ENCLOSURE WITH A STAIRWAY. THE 1ST FLOOR
 AND MEZZANINE LEVEL WOULD BE OK SINCE THE MEZZANINE
 LEVEL IS NOT CONSIDERED A STORY. HOW WILL SMOKE
 ACCUMULATION IN THE STAIRWELL BE HANDLED SINCE THE
 FLOOR BELOW (MEZZANINE LEVEL) IS OPEN.
  
 4E) THE SECOND FLOOR FRONT STAIRWELL WILL NEED TO
 INDICATE FIRE RATING ON THE WALLS AND OPENING
 PENETRATIONS. FBC 1020.1 & TABLE 715.4. SHEET A8.03
 INDICATES WALL RATINGS BUT THE FLOOR PLANS DO NOT TIE
 THEM TO ANY WALLS WITH WALL MARKERS. THE SAME HOLDS
 TRUE FOR RATING OF FIRE RATED DOORS THE DOOR SCHEDULE
 DOES NOT PROVIDE ANY DOOR OPENINGS THAT WOULD REQUIRE
 FIRE RATING, STAIRWELL ENTRY DOORS, THE 2ND FLOOR
 STAIRWELL,
  
 5) PROVIDE THE OCCUPANT LOADS PER 2007/09 FBC-B
 106.3.5.1.1(7) OCCUPANT LOADS FOR EACH OF THE ASSEMBLY
 AREAS WITH BREAKDOWN IF 5 NET, 7 NET OR 15 NET, PER
 FLOOR AND FOR THE BUSINESS OCCUPANCY. FBC-B TABLE
 1004.1.1.
  
 6) SHEET A-1 ALSO FAILS TO PROVIDE INFORMATION ON
 OCCUPANCY SEPARATION BETWEEN THE A2 OCCUPANCY AND THE
 BUSINESS OCCUPANCY LOCATED ON THE 2ND FLOOR, PLEASE
 PROVIDE DESIGN CRITERIA 2007/09 FBC-B 508.3.1.3.
  
 7) DEPENDING ON THE OCCUPANT LOAD OF THE A2 OCCUPANCY
 THIS BUILDING MAY END UP BEING CLASSIFIED AS A
 THRESHOLD BUILDINGREQIRING THE FOLLOWING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 7A)109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 7B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 7C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7D) A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE
 ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 8) PLEASE PROVIDE INFORMATION AS TO SHEET A-6 WHAT IS
 THE ROOM # 119 USED FOR IS THIS THE ELEVATOR MACHINE
 ROOM? IF SO IT NEEDS TO BE RATED AS DOES THE DOOR.
  
 9) SHEET A-6 & S-2 INDICATES NEW RAISED PLATFORM
 FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF RAISED
 PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09 FBC-B
 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
  
 10) IT APPEARS THERE MAY BE A DISCREPANCY BETWEEN A-6 &
 S-2, ON SHEET S-2 IT APPEARS THERE IS A DOORWAY THAT
 LEADS FROM THE RAISED DECK IN TO THE STAIRWELL WITH NO
 LANDING OR STAIRS. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 11) ADDITIONAL INFORMATION REQUIRED, SHEET A8.01
 INDICATES THE USE OF A NEW ROOF HATCH WHICH IS NOT
 INDICATED ON EITHER THE ARCHITECTURAL NOR STRUCTURAL
 SHEETS. SHEET A8 IN STORAGE ROOM 304-A HAS WHAT APPEARS
 TO BE A LADDER AND POSSIBLE LOCATION FOR THE ROOF HATCH
 THE SECTION 11/ A-16 DOES NOT MATCH UP WITH ANY PLANS
 WITHIN THIS SET, ADDITIONAL INFORMATION IS REQUIRED.
 PLEASE REVIEW 2007/09 FBC-B 1509.6 FOR PERMANENT LADDER
 REQUIREMENTS. PLEASE REVIEW 2007/09 MECH CODE 304.10
 FOR GUARD REQUIREMENTS WHEN UNITS ARE WITHIN 10?-0? OF
 THE ROOF EDGE.
  
 12) SHEET A-21 EAST ELEVATION INDICATES THE USE OF AN
 EXISTING FIRE ESCAPE EXIT DOORS AND WINDOW # 12 BEING
 REPLACED. PLEASE REVIEW 2007/09 EXST BLDG CODE 303.5
 OPENING PROTECTION. DOORS AND WINDOWS ALONG THE FIRE
 ESCAPE SHALL BE PROTECTED WITH ? HR OPENING
 PROTECTIVES.
  
 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) WINDOWS
 13B) ROOF HATCH
 13C) A/C PRE-MANUFACTURED STANDS
  
 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15A) SHEET A-53 STAIR DESIGN NEEDS TO BE UPDATED FROM
 THE 1997 UBC.
  
 15B) SHEET A-53 STAIR NOTE # 3 PLEASE UPDATE NOTE TO
 THE 2007/09 FBC-B 1607.1.2
 INTERMEDIATE RAILS SHALL BE DESIGNED TO WITHSTAND
 HORIZONTALLY
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  