Text |
| 2011-05-31 15:04:50 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 11050596 |
| | ADD: 114 S OLIVE AVE |
| | CONT: LAKESIDE CONTRACTING CORP |
| | TEL: (954)553-8398 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE PLANS OF THE EXISTING SPACE |
| | INDICATING WHERE THE STAIRWELLS AND EXISTING EXIT |
| | LOCATIONS. IT APPEARS THE MEZZANINE IS A NEW LEVEL? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. 2007/09 FL |
| | EXST BLDG CODE 701.3 NEW WORK. |
| | |
| | 2) WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, IS |
| | THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT REFERENCE |
| | THE FLORIDA EXISTING BUILDING CODE AND TO WHICH TYPE OF |
| | COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO? FL EXST |
| | BLDG CODE 101.5 (.1-.3). |
| | |
| | 3A) SHEET A-1.0 THE BUILDING & CODE INFORMATION |
| | INDICATES THIS BUILDING TYPE UNDER THE 1997 UBC AS A |
| | TYPE II-B NON-COMBUSTIBLE/ NONRATED. PLEASE REFER TO |
| | THE 2007 FBC-B FOR BUILDING TYPE, NOTE THE 2007FBC-B |
| | 603.1.3 REQUIRES ALL ROOF CONSTRUCTION GIRDERS, JOIST, |
| | TRUSSES AND DECKING ARE TO BE FIRE RETARDANT TREATED |
| | WOOD. SHEET S-5 INDICATES THE EXISTING 2X6 ROOF |
| | FRAMING, IS THE EXISTING STRUCTURE TRULY A BUILDING |
| | TYPE II-B? PLEASE NOTE THE NEW FRAMING MEMBERS LOCATED |
| | ON SHEET S-5 DO NOT INDICATE THE USE OF FIRE RETARDANT |
| | TREATED WOOD. |
| | |
| | 3B) THE BUILDING & CODE INFORMATION FOUND ON SHEET A-1 |
| | DOES NOT INDICATE IF THIS IS A FIRE SPRINKLERED |
| | BUILDING? 2007/09 FBC-B 106.3.5.1.1. MINIMUM PLAN |
| | REVIEW CRITERIA. |
| | |
| | 4A) PLEASE PROVIDE A LIFE SAFETY PLAN W/ FURNISHINGS |
| | OCCUPANT LOADS & EGRESS CAPACITIES. 2007/09 FBC-B |
| | 106.3.5.1.1(6). |
| | |
| | 4B) PLEASE PROVIDE COMMON PATH OF TRAVEL FOR THE FIRST |
| | FLOOR SEE LIMITATIONS 1014.3 FOR THE FIRST FLOOR AS |
| | WELL AS THE MEZZANINE LEVEL AND THE SECOND FLOOR. |
| | REVIEW SECTION 505.3 FOR THE MEZZANINE MAXIMUM TRAVEL |
| | DISTANCE INCLUDES THE DISTANCE TRAVELED ON THE STAIRWAY |
| | MEASURED IN THE PLANE OF THE TREAD NOSING. |
| | |
| | 4C) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE |
| | OCCUPANCY SEPARATION IN CONJUNCTION TO THE OPEN AIR |
| | STAIR BETWEEN THE MEZZANINE LEVEL AND THE 2ND FLOOR |
| | LEVEL? |
| | 2007 FBC-B TABLE 508.3.3. |
| | |
| | 4D) THE SECOND FLOOR FRONT STAIRWAY IS IN THE SAME |
| | STAIRWELL AS THE ELEVATOR. 2007 FBC-B 3002.7 COMMON |
| | ENCLOSURE WITH STAIRWAY. ELEVATORS SHALL NOT BE IN A |
| | COMMON SHAFT ENCLOSURE WITH A STAIRWAY. THE 1ST FLOOR |
| | AND MEZZANINE LEVEL WOULD BE OK SINCE THE MEZZANINE |
| | LEVEL IS NOT CONSIDERED A STORY. HOW WILL SMOKE |
| | ACCUMULATION IN THE STAIRWELL BE HANDLED SINCE THE |
| | FLOOR BELOW (MEZZANINE LEVEL) IS OPEN. |
| | |
| | 4E) THE SECOND FLOOR FRONT STAIRWELL WILL NEED TO |
| | INDICATE FIRE RATING ON THE WALLS AND OPENING |
| | PENETRATIONS. FBC 1020.1 & TABLE 715.4. SHEET A8.03 |
| | INDICATES WALL RATINGS BUT THE FLOOR PLANS DO NOT TIE |
| | THEM TO ANY WALLS WITH WALL MARKERS. THE SAME HOLDS |
| | TRUE FOR RATING OF FIRE RATED DOORS THE DOOR SCHEDULE |
| | DOES NOT PROVIDE ANY DOOR OPENINGS THAT WOULD REQUIRE |
| | FIRE RATING, STAIRWELL ENTRY DOORS, THE 2ND FLOOR |
| | STAIRWELL, |
| | |
| | 5) PROVIDE THE OCCUPANT LOADS PER 2007/09 FBC-B |
| | 106.3.5.1.1(7) OCCUPANT LOADS FOR EACH OF THE ASSEMBLY |
| | AREAS WITH BREAKDOWN IF 5 NET, 7 NET OR 15 NET, PER |
| | FLOOR AND FOR THE BUSINESS OCCUPANCY. FBC-B TABLE |
| | 1004.1.1. |
| | |
| | 6) SHEET A-1 ALSO FAILS TO PROVIDE INFORMATION ON |
| | OCCUPANCY SEPARATION BETWEEN THE A2 OCCUPANCY AND THE |
| | BUSINESS OCCUPANCY LOCATED ON THE 2ND FLOOR, PLEASE |
| | PROVIDE DESIGN CRITERIA 2007/09 FBC-B 508.3.1.3. |
| | |
| | 7) DEPENDING ON THE OCCUPANT LOAD OF THE A2 OCCUPANCY |
| | THIS BUILDING MAY END UP BEING CLASSIFIED AS A |
| | THRESHOLD BUILDINGREQIRING THE FOLLOWING: |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 7A)109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 7B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 7C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 7D) A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE |
| | ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONCRETE RESTORATION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 8) PLEASE PROVIDE INFORMATION AS TO SHEET A-6 WHAT IS |
| | THE ROOM # 119 USED FOR IS THIS THE ELEVATOR MACHINE |
| | ROOM? IF SO IT NEEDS TO BE RATED AS DOES THE DOOR. |
| | |
| | 9) SHEET A-6 & S-2 INDICATES NEW RAISED PLATFORM |
| | FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF RAISED |
| | PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09 FBC-B |
| | 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT. |
| | |
| | 10) IT APPEARS THERE MAY BE A DISCREPANCY BETWEEN A-6 & |
| | S-2, ON SHEET S-2 IT APPEARS THERE IS A DOORWAY THAT |
| | LEADS FROM THE RAISED DECK IN TO THE STAIRWELL WITH NO |
| | LANDING OR STAIRS. 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 11) ADDITIONAL INFORMATION REQUIRED, SHEET A8.01 |
| | INDICATES THE USE OF A NEW ROOF HATCH WHICH IS NOT |
| | INDICATED ON EITHER THE ARCHITECTURAL NOR STRUCTURAL |
| | SHEETS. SHEET A8 IN STORAGE ROOM 304-A HAS WHAT APPEARS |
| | TO BE A LADDER AND POSSIBLE LOCATION FOR THE ROOF HATCH |
| | THE SECTION 11/ A-16 DOES NOT MATCH UP WITH ANY PLANS |
| | WITHIN THIS SET, ADDITIONAL INFORMATION IS REQUIRED. |
| | PLEASE REVIEW 2007/09 FBC-B 1509.6 FOR PERMANENT LADDER |
| | REQUIREMENTS. PLEASE REVIEW 2007/09 MECH CODE 304.10 |
| | FOR GUARD REQUIREMENTS WHEN UNITS ARE WITHIN 10?-0? OF |
| | THE ROOF EDGE. |
| | |
| | 12) SHEET A-21 EAST ELEVATION INDICATES THE USE OF AN |
| | EXISTING FIRE ESCAPE EXIT DOORS AND WINDOW # 12 BEING |
| | REPLACED. PLEASE REVIEW 2007/09 EXST BLDG CODE 303.5 |
| | OPENING PROTECTION. DOORS AND WINDOWS ALONG THE FIRE |
| | ESCAPE SHALL BE PROTECTED WITH ? HR OPENING |
| | PROTECTIVES. |
| | |
| | 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 13A) WINDOWS |
| | 13B) ROOF HATCH |
| | 13C) A/C PRE-MANUFACTURED STANDS |
| | |
| | 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 15A) SHEET A-53 STAIR DESIGN NEEDS TO BE UPDATED FROM |
| | THE 1997 UBC. |
| | |
| | 15B) SHEET A-53 STAIR NOTE # 3 PLEASE UPDATE NOTE TO |
| | THE 2007/09 FBC-B 1607.1.2 |
| | INTERMEDIATE RAILS SHALL BE DESIGNED TO WITHSTAND |
| | HORIZONTALLY |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |