2011-06-21 10:10:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE GENERAL BUILDING CODE ANALYSIS AND CODE
 TABULATION, ONE STATES THAT THIS IS A LEVEL 1
 ALTERATION, THE OTHER STATES THIS IS A LEVEL 2. PLEASE
 CORRELATE (SHOULD BE LEVEL 2, FBC EXISTING BUILDING
 404).
  
 2. EXISTING OCCUPANCY CLASSIFICATION AND PROPOSED
 OCCUPANCY CLASSIFICATION IS UNCLEAR. PLAN STATES THIS
 IS BUSINESS, BUT THERE ARE REFERENCES TO "STORES" AND
 "RETAIL" ON THE PERMIT DOCUMENTS AND PLAN. PLEASE
 CLARIFY WHETHER OR NOT THIS IS A CHANGE OF OCCUPANCY.
 STATE CLEARLY EXISTING OCCUPANCY OF THIS SPACE,
 PROPOSED OCCUPANCY FOR THIS SPACE. OTHER INFORMATION
 REGARDING THE BUILDING CAN BE INCLUDED IF APPLICABLE
 BUT SHOULD BE NOTED AS EXISTING OR OTHER TENANTS.
  
 3. PLAN STATES THIS IS "PROPOSED COMMON AREA." COMMON
 AREA FOR THE BUILDING OR A TENANT? IT IS NOT CLEAR HOW
 FIRE RATED WALLS WILL BE AFFECTED. FBC 708.1.
  