| Plan Review Notes For Permit 11050566 |
| Permit Number |
11050566 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-21 10:10:30 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE GENERAL BUILDING CODE ANALYSIS AND CODE | | | TABULATION, ONE STATES THAT THIS IS A LEVEL 1 | | | ALTERATION, THE OTHER STATES THIS IS A LEVEL 2. PLEASE | | | CORRELATE (SHOULD BE LEVEL 2, FBC EXISTING BUILDING | | | 404). | | | | | | 2. EXISTING OCCUPANCY CLASSIFICATION AND PROPOSED | | | OCCUPANCY CLASSIFICATION IS UNCLEAR. PLAN STATES THIS | | | IS BUSINESS, BUT THERE ARE REFERENCES TO "STORES" AND | | | "RETAIL" ON THE PERMIT DOCUMENTS AND PLAN. PLEASE | | | CLARIFY WHETHER OR NOT THIS IS A CHANGE OF OCCUPANCY. | | | STATE CLEARLY EXISTING OCCUPANCY OF THIS SPACE, | | | PROPOSED OCCUPANCY FOR THIS SPACE. OTHER INFORMATION | | | REGARDING THE BUILDING CAN BE INCLUDED IF APPLICABLE | | | BUT SHOULD BE NOTED AS EXISTING OR OTHER TENANTS. | | | | | | 3. PLAN STATES THIS IS "PROPOSED COMMON AREA." COMMON | | | AREA FOR THE BUILDING OR A TENANT? IT IS NOT CLEAR HOW | | | FIRE RATED WALLS WILL BE AFFECTED. FBC 708.1. | | | |
|