| 2011-06-24 12:19:04 | 215 SOUTH OLIVE AVENUE | | | PERMIT #11050566 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | PLAN INDICATES THE CONSTRUCTION TYPE AS 5B | | | UNSPRINKLERED. I BELIEVE THIS BUILDING IS FULLY | | | SPRINKLERED. | | | | | | INDICATE SAFETY MEASURES TO PREVENT AN OCCUPANT FROM | | | BEING LOCKED IN THE VAULT ROOM. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND FIRE ALARM SYSTEM. SPRINKLERS MAY BE NEEDED | | | IN THE STORAGE/VAULT ROOM IF THEY ARE NOT ALREADY | | | EXISTING. | | | | | | THE PLANS INDICATE THE SPACE IS RETAIL OCCUPANCY BUT | | | THE OCCUPANT LOAD FACTOR WAS DETERMINED BASED UPON | | | BUSINESS OCCUPANCY. | | | | | | PROVIDE FURNITURE/STORE LAYOUT PLAN. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|