Plan Review Notes
Plan Review Notes For Permit 11050566
Permit Number 11050566
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-06-24 12:19:04215 SOUTH OLIVE AVENUE
 PERMIT #11050566
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PLAN INDICATES THE CONSTRUCTION TYPE AS 5B
 UNSPRINKLERED. I BELIEVE THIS BUILDING IS FULLY
 SPRINKLERED.
  
 INDICATE SAFETY MEASURES TO PREVENT AN OCCUPANT FROM
 BEING LOCKED IN THE VAULT ROOM.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM. SPRINKLERS MAY BE NEEDED
 IN THE STORAGE/VAULT ROOM IF THEY ARE NOT ALREADY
 EXISTING.
  
 THE PLANS INDICATE THE SPACE IS RETAIL OCCUPANCY BUT
 THE OCCUPANT LOAD FACTOR WAS DETERMINED BASED UPON
 BUSINESS OCCUPANCY.
  
 PROVIDE FURNITURE/STORE LAYOUT PLAN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  