Plan Review Notes
Plan Review Notes For Permit 11050554
Permit Number 11050554
Review Stop M
Sequence Number 1
Notes
Date Text
2011-06-20 09:54:59REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2.2: DRYER EXHAUST IS SHOWN BEING ROUTED
 THROUGH A RETURN AIR PLENUM CEILING SPACE. EXHAUST
 TUCTS UNDER POSITIVE PRESSURE SHALL NOT PASS THROUGH A
 PLENUM PER FBC-M 601.5.
  
 2. PAGE M-2.2: PLAN SHOWS A DRYER BOOSTER FAN TO BE
 USED. PROVIDE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING THAT A BOOSTER FAN MAY BE USED
 WITH THESE SPECIFIC DRYERS. CLOTHES DRYERS SHALL BE
 EXHAUSTED IN ACCORDANCE WITH THE DRYER MANUFACTURER'S
 INSTRUCTIONS PER FBC-M 504.1.
  
 3. PAGE M-2.2 SHOWS TWO DRYER EXHAUST DUCTS BEING
 MANIFOLDED INTO ONE DUCT. NO DUCT SIZES ARE PROVIDED ON
 PLAN. THIS CONDITION MUST ALSO BE COVERED BY THE DRYER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER FBC-M
 504.1.
  
 4. PAGE M-2.2: PLAN CALLS FOR DRYER EXHAUST TO
 TERMINATE AT A GRS-8 ROOF VENT. WHERE WILL THE
 BACKDRAFT DAMPER FOR THE DRYER EXHAUST BE LOCATED? IS
 THE GRS-8 ROOF VENT OPENING SCREENED? BACKDRAFT DAMPER
 IS REQUIRED ON DRYER EXHAUST DUCT OUTLETS AND SCREENS
 ARE PROHIBITED PER FBC-M 504.4.
  