| Notes |
| Date |
Text |
| 2011-06-20 09:54:59 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-2.2: DRYER EXHAUST IS SHOWN BEING ROUTED | | | THROUGH A RETURN AIR PLENUM CEILING SPACE. EXHAUST | | | TUCTS UNDER POSITIVE PRESSURE SHALL NOT PASS THROUGH A | | | PLENUM PER FBC-M 601.5. | | | | | | 2. PAGE M-2.2: PLAN SHOWS A DRYER BOOSTER FAN TO BE | | | USED. PROVIDE DRYER MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS SHOWING THAT A BOOSTER FAN MAY BE USED | | | WITH THESE SPECIFIC DRYERS. CLOTHES DRYERS SHALL BE | | | EXHAUSTED IN ACCORDANCE WITH THE DRYER MANUFACTURER'S | | | INSTRUCTIONS PER FBC-M 504.1. | | | | | | 3. PAGE M-2.2 SHOWS TWO DRYER EXHAUST DUCTS BEING | | | MANIFOLDED INTO ONE DUCT. NO DUCT SIZES ARE PROVIDED ON | | | PLAN. THIS CONDITION MUST ALSO BE COVERED BY THE DRYER | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER FBC-M | | | 504.1. | | | | | | 4. PAGE M-2.2: PLAN CALLS FOR DRYER EXHAUST TO | | | TERMINATE AT A GRS-8 ROOF VENT. WHERE WILL THE | | | BACKDRAFT DAMPER FOR THE DRYER EXHAUST BE LOCATED? IS | | | THE GRS-8 ROOF VENT OPENING SCREENED? BACKDRAFT DAMPER | | | IS REQUIRED ON DRYER EXHAUST DUCT OUTLETS AND SCREENS | | | ARE PROHIBITED PER FBC-M 504.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|