| Plan Review Notes For Permit 11050497 |
| Permit Number |
11050497 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-07 15:08:14 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE SECOND FLOOR BATH ROOM IS NOT VENTED CORECTLY. | | | FBC R3108.2 ONLY ALLOWS ONE WET-VENTED FIXTURE DRAIN TO | | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | | CONNECTION. | | | | | | 2) THE 2" WASHING MACHINE DRAIN IS REQUIRED TO CONNECT | | | TO A MINIMUM 3" DIAMETER BRANCH DRAIN OR DRAINAGE STACK | | | PER FBC P 406.3. | | | | | | 3) IS THE LAUNDRY ROOM FOR THE USE OF THE TWO UNITS IN | | | THIS BUILDING ONLY? SPECIFY THE NUMBER OF UNITS THAT | | | WILL BE USING THE LAUNDRY ROOM ON THE PLANS. FBC P412.4 | | | | | | 4) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|