| 2011-06-08 11:21:07 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE WRONG EXPOSURE CATEGORY IS SPECIFIED ON THE |
| | PLANS. THE CORRECT EXPOSURE IS 'C' PER FBC R |
| | 301.2.1.4.3. |
| | |
| | 2) THE STRUCTURE IS NOT A SINGLE FAMILY HOME BECAUSE IT |
| | HAS TWO SEPARATE DWELLING UNITS. IT IS A TWO-FAMILY |
| | DWELLING. FBCR CHAPTER 2. |
| | |
| | 3) SPECIFY THE ONE HOUR FIRE-RESISTANCE RATED |
| | FLOOR/CEILING TESTED ASSEMBLY THAT WILL BE INSTALLED. |
| | PROVIDE A SECTION DETAIL OF THE TESTED ASSEMBLY WITH |
| | THE FILE OR LISTING NUMBER. FBC R 317.1 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R317.1.1 SUPPORTING |
| | CONSTRUCTION WHICH REQUIRES THE WALLS SUPPORTING THE |
| | ONE HOUR FIRE-RESISTANCE RATED FLOOR/CEILING TO HAVE AN |
| | EQUAL OR GREATER FIRE-RESISTIVE RATING. PROVIDE A |
| | SECTION DETAIL OF THE TESTED ASSEMBLY WITH THE FILE OR |
| | LISTING NUMBER. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R317.3 WHICH REQUIRES |
| | PENETRATIONS OF FIRE-RESISTANCE RATED WALL OR |
| | FLOOR/CEILING ASSEMBLIES TO BE PROTECTED. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R602.1.2 FOR THE FIRE |
| | BLOCKING THAT IS REQUIRED IN THE BALLOON FRAMED WALLS |
| | AT THE CEILING AND FLOOR LEVELS. |
| | |
| | 7) THE BEARING WALL SUPPORTING THE FLOOR/CEILING |
| | ASSEMBLY IS NOT SHOWN AS BEING CONTINUOUS ON THE PLANS. |
| | PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE FLOOR |
| | JOISTS ARE BEING AT THE OPENING TO THE FIRST FLOOR |
| | KITCHEN. FBC R601.2 |
| | |
| | 8) THE PLANS SPECIFY 2 X 6 FLOOR JOISTS AT 16" OC |
| | SPANNING MORE THAN 13 FEET WITH A REQUIRED LIVE LOAD OF |
| | 40 PSF. THIS EXCEEDS THE ALLOWABLE JOIST SPANS OF FBCR |
| | TABLE R502.2.3(2). |
| | |
| | 9) THE STAIRWAYS AND HANDRAILS ARE REQUIRED TO COMPLY |
| | WITH FBC R311.5. THE PLANS SITE SBC 1608.2.1 AND 1007 |
| | WHICH NO LONGER APPLY. CORRECT SHEET A-3. |
| | |
| | 10) THE GUARDS ARE REQUIRED TO COMPLY WITH FBC R312. |
| | CORRECT SHEET A-3. |
| | |
| | 11) THE OPENINGS FOR THE GUARDS SHOWN ON A-2 OF THE |
| | PLANS, DO NOT COMPLY WITH FBC R312.2 GUARD OPENING |
| | LIMITATIONS. THE OPENINGS FOR GUARDS ON THE SIDES OF |
| | STAIR TREADS SHALL NOT ALLOW A 4-3/8" DIA. SPHERE TO |
| | PASS THROUGH. |
| | |
| | 12) THE PLANS INDICATE A NEW EXTERIOR DOOR INSTALLED ON |
| | THE LAUNDRY ROOM. SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR THE DOOR AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 106.3.3 |
| | |
| | 14) THE SCOPE OF WORK DOES NOT INDICATE THAT THE |
| | WINDOWS ARE BEING REPLACED, HOWEVER, A WINDOW LEGEND IS |
| | SPECIFIED ON SHEET A-1. IF THE WINDOWS ARE TO BE |
| | REPLACED PROVIDE THE APPROPRIATE PRODUCT APPROVALS AS |
| | REQUIRED BY DCA RULE 9N-3. |
| | |
| | 15) SPECIFY ON THE PLANS THE DWELLING UNITS THAT WILL |
| | HAVE USE OF THE LAUNDRY ROOM. FBC R101.2 |
| | |
| | 16) THE SHARED LAUNDRY ROOM WILL BE REQUIRED TO HAVE |
| | ONE HOUR FIRE-RESISTANCE RATED SEPARATION FROM BOTH |
| | UNITS. FBC R317.1 |
| | |
| | 17) SUBMIT A RESPONSE LETTER INDICATING HOW THE REVIEW |
| | COMMENTS HAVE BEEN ADDRESSED. |
| | |