2011-10-20 11:44:47****CORRECTIONS****
 (REVISED 11/7/11)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. PROVIDE MORE INFORMATION REGARDING THE OCCUPANCY OF
 THIS BUILDING. SEE ZONING COMMENTS. IF A CHANGE OF
 OCCUPANCY IS INVOLVED, SHOW COMPLIANCE.
  
 2ND REVIEW, LETTER STATES THAT THERE IS NO BATHROOM OR
 KITCHEN, OWNER USING THE ADJACENT SPACE FOR STORAGE.
 HOWEVER, THERE IS A CURRENT BUSINESS TAX FOR APARTMENT,
 AND ARCHITECT'S PROPOSED SITE PLAN SHOWS THIS AS AN
 APARTMENT. IT APPEARS THAT A CHANGE OF OCCUPANCY WAS
 DONE WITHOUT PERMIT. PLEASE INCLUDE THE CONVERSION OF
 THE RESIDENTIAL SPACE TO STORAGE OCCUPANCY IN THE SCOPE
 OF THIS PERMIT. SEE FBC EXISTING BUILDING CODE FOR
 REQUIREMENTS FOR A CHANGE OF OCCUPANCY.
  
 COURTESY REVIEW 11/7/11 - PER ADDRESSING, THIS ADDRESS
 WAS IMPROPERLY USED BY ANOTHER ENTITY AND LOCATION.
 PLEASE CONSIDER THE COMMENT REGARDING CHANGE OF
 OCCUPANCY AS RESOLVED.
  
 2. REVISE EXPOSURE CATEGORY OR PROVIDE RATIONAL
 ANALYSIS CALCULATIONS FOR USE OF EXPOSURE B PRESSURES.
 FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED
 EFFECTIVE MARCH 1, 2009.
  
 PLANS STILL STATE EXPOSURE B, PLEASE ADDRESS PREVIOUS
 COMMENT. DESIGN PRESSURES ON A4 TOO LOW FOR EXPOSURE C.
 LETTER REFERS TO SP1, CANNOT LOCATE THIS SHEET IN
 PERMIT PACKAGE.
  
 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, ALSO SEE
 ARCHITECT'S REQUIREMENTS ON SHEET A3. NON IMPACT
 PRODUCT APPROVALS SUBMITTED.
  
 2ND REVIEW, IMPACT PRODUCT APPROVALS SUBMITTED.
 HOWEVER, PLEASE NOTE THE FOLLOWING:\
  
 PGT FRENCH DOOR PRODUCT APPROVALS SUBMITTED, NOT CLEAR
 WHERE THIS WILL BE INSTALLED, AND THIS BRAND IS
 INTENDED FOR RESIDENTIAL USE AND DOES NOT COMPLY WITH
 THE REQUIREMENTS OF FBC CHAPTER 11 (SEE THRESHOLD
 HEIGHT ON PRODUCT APPROVAL, ALSO PER MANUFACTURER).
  
 4. SEE OTHER COMMENT REGARDING THE OCCUPANCY OF THIS
 BUILDING. PLANS STATE THAT THIS IS AN "EXISTING
 SHOWROOM" WHICH WOULD IMPLY MERCANTILE. NON IMPACT
 RESIDENTIAL DOOR PRODUCT APPROVAL WAS SUBMITTED.
 ARCHITECT HAS SPECIFIED PANIC BARS. THIS IS NOT
 INCLUDED IN THE PRODUCT APPROVAL. SILL HEIGHT ON THE
 DOOR PRODUCT APPROVAL EXCEEDS THE DIMENSION PERMITTED
 BY FBC11-4.5.2, PRODUCT APPROVAL DOES NOT INCLUDE PANIC
 BARS.
  
 IT APPEARS THAT PROPOSED USE (OR PERHAPS EXISTING USE,
 DONE WITHOUT PERMIT) IS MERCANTILE, BUSINESS, AND
 STORAGE. REVISE PLAN TO SHOW COMPLIANCE WITH CHANGE OF
 OCCUPANCY FROM RESIDENTIAL TO STORAGE, SEE OTHER
 COMMENTS. SEE FBC EXISTING BUILDING CHAPTER 9. IF YOU
 BELIEVE THAT A CHANGE OF OCCUPANCY WAS DONE PREVIOUSLY
 THROUGH THE BUILDING DEPARTMENT AS REQUIRED BY FBC
 105.1, PLEASE PROVIDE DOCUMENTATION (PERMIT NUMBER) AND
 EXPLAIN THE APARTMENT BUSINESS TAX RECEIPT (FORMERLY
 CALLED "OCCUPATIONAL LICENSE") FOR THIS STRUCTURE.
  
 COURTESY REVIEW 11/7/11 - PER ARCHITECT, BUILDING IS
 EXISTING; MERCANTILE, BUSINESS, AND STORAGE.
  
 5-7. ADDRESSED.
  
 NEW COMMENTS:
  
 8. SLIDING DOORS ARE NOW SHOWN IN THE PLAN, SHOW
 COMPLIANCE WITH FBC1008.1.3.3. THE SLIDING GLASS DOOR
 PRODUCT APPROVAL IS A RESIDENTIAL DOOR, PLEASE SUBMIT
 APPROPRIATE PRODUCT APPROVAL.
  
 9. AS NO MECHANICAL INFORMATION WAS PROVIDED,
 MECHANICAL REVIEW WILL NOT BE DONE ON THIS REVIEW.
 PLEASE PROVIDE INFORMATION TO SHOW COMPLIANCE WITH FBC
 EXISTING BUIDLING 709.1 AND 909 (EXHAUST FOR BATHROOMS,
 VENTILATION (OUTDOOR AIR) FBC MECHANICAL CHAPTER 4).
  
 COURTESY REVIEW 11/7/11, N/A (PLEASE DISREGARD #9)
  
 10. PROVIDE A DETAIL FOR THE RAMP, FBC 11-4.8. ALSO SEE
 MANEUVERING CLEARANCE FOR DOORS, FBC 11 FIGURE 25 AND
 REVISE PLAN TO SHOW MINIMUM DIMENSIONS.
  
 11. PROVIDE A COST BREAKDOWN FOR THIS JOB, SEE FBC
 11-4.1.6(2).
  
  
  