| 2011-06-02 14:42:14 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PROVIDE MORE INFORMATION REGARDING THE OCCUPANCY OF |
| | THIS BUILDING. SEE ZONING COMMENTS. IF A CHANGE OF |
| | OCCUPANCY IS INVOLVED, SHOW COMPLIANCE. |
| | |
| | 2. REVISE EXPOSURE CATEGORY OR PROVIDE RATIONAL |
| | ANALYSIS CALCULATIONS FOR USE OF EXPOSURE B PRESSURES. |
| | FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED |
| | EFFECTIVE MARCH 1, 2009. |
| | |
| | 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, ALSO SEE |
| | ARCHITECT'S REQUIREMENTS ON SHEET A3. NON IMPACT |
| | PRODUCT APPROVALS SUBMITTED. |
| | |
| | 4. SEE OTHER COMMENT REGARDING THE OCCUPANCY OF THIS |
| | BUILDING. PLANS STATE THAT THIS IS AN "EXISTING |
| | SHOWROOM" WHICH WOULD IMPLY MERCANTILE. NON IMPACT |
| | RESIDENTIAL DOOR PRODUCT APPROVAL WAS SUBMITTED. |
| | ARCHITECT HAS SPECIFIED PANIC BARS. THIS IS NOT |
| | INCLUDED IN THE PRODUCT APPROVAL. SILL HEIGHT ON THE |
| | DOOR PRODUCT APPROVAL EXCEEDS THE DIMENSION PERMITTED |
| | BY FBC11-4.5.2, PRODUCT APPROVAL DOES NOT INCLUDE PANIC |
| | BARS. |
| | |
| | 5. PLEASE PROVIDE A SITE PLAN TO SHOW LOCATION OF |
| | PROPOSED IMPROVEMENTS IN RELATION TO THE PROPERTY LINE. |
| | A COMPLETE PLAN REVIEW CANNOT BE PERFORMED AT THIS |
| | TIME. |
| | |
| | 6. PLEASE REVISE PLAN TO SHOW WHETHER A1 IS "PROPOSED |
| | FLOOR PLAN" OR "EXISTING FLOOR PLAN." IF THIS IS |
| | "PROPOSED," IT IS NOT CLEAR HOW PANIC HARDWARE WILL |
| | OPERATE ON AN INSWING DOOR. |
| | |
| | 7. DOOR HARDWARE TO COMPLY WITH FBC1008.1.4, PLEASE |
| | PROVIDE SPECS TO SHOW COMPLIANCE IF NOT INCLUDED IN THE |
| | PRODUCT APPROVAL. |
| | |
| | |
| | |