2011-06-02 14:42:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE MORE INFORMATION REGARDING THE OCCUPANCY OF
 THIS BUILDING. SEE ZONING COMMENTS. IF A CHANGE OF
 OCCUPANCY IS INVOLVED, SHOW COMPLIANCE.
  
 2. REVISE EXPOSURE CATEGORY OR PROVIDE RATIONAL
 ANALYSIS CALCULATIONS FOR USE OF EXPOSURE B PRESSURES.
 FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED
 EFFECTIVE MARCH 1, 2009.
  
 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, ALSO SEE
 ARCHITECT'S REQUIREMENTS ON SHEET A3. NON IMPACT
 PRODUCT APPROVALS SUBMITTED.
  
 4. SEE OTHER COMMENT REGARDING THE OCCUPANCY OF THIS
 BUILDING. PLANS STATE THAT THIS IS AN "EXISTING
 SHOWROOM" WHICH WOULD IMPLY MERCANTILE. NON IMPACT
 RESIDENTIAL DOOR PRODUCT APPROVAL WAS SUBMITTED.
 ARCHITECT HAS SPECIFIED PANIC BARS. THIS IS NOT
 INCLUDED IN THE PRODUCT APPROVAL. SILL HEIGHT ON THE
 DOOR PRODUCT APPROVAL EXCEEDS THE DIMENSION PERMITTED
 BY FBC11-4.5.2, PRODUCT APPROVAL DOES NOT INCLUDE PANIC
 BARS.
  
 5. PLEASE PROVIDE A SITE PLAN TO SHOW LOCATION OF
 PROPOSED IMPROVEMENTS IN RELATION TO THE PROPERTY LINE.
 A COMPLETE PLAN REVIEW CANNOT BE PERFORMED AT THIS
 TIME.
  
 6. PLEASE REVISE PLAN TO SHOW WHETHER A1 IS "PROPOSED
 FLOOR PLAN" OR "EXISTING FLOOR PLAN." IF THIS IS
 "PROPOSED," IT IS NOT CLEAR HOW PANIC HARDWARE WILL
 OPERATE ON AN INSWING DOOR.
  
 7. DOOR HARDWARE TO COMPLY WITH FBC1008.1.4, PLEASE
 PROVIDE SPECS TO SHOW COMPLIANCE IF NOT INCLUDED IN THE
 PRODUCT APPROVAL.
  
  
  