| Plan Review Notes For Permit 11050433 |
| Permit Number |
11050433 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-27 10:46:14 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PRESSURES ARE TOO LOW. REVISE EXPOSURE TO CATEGORY C | | | OR PROVIDE RATIONAL ANALYSIS FOR REDUCED PRESSURES. | | | FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED | | | EFFECTIVE MARCH 1, 2009. | | | | | | 2. SPANS ARE NOT CORRECT; WITH A WALL MOUNT, THIS | | | SHOULD BE LARGER THAN THE OPENING DIMENSION. SPAN FOR | | | ACCORDION SHUTTERS SHOULD EQUAL THE BLADE LENGTH. | | | | | | 3. EITHER REVISE BOTTOM SUBSTRATE TO BLOCK OR PROVIDE | | | INFORMATION AS TO HOW YOU HAVE DETERMINED THAT THE | | | BOTTOM SUBSTRATE IS CONCRETE. CBS HOMES TYPICALLY HAVE | | | CONCRETE TOP, BLOCK BOTTOM SUBSTRATE. A FILLED CELL | | | REQUIRES USE OF BLOCK SUBSTRATE UNLESS THE PRODUCT | | | APPROVAL INCLUDES FILLED CMU AS A SUBSTRATE. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE. | | | | | | |
|