| Plan Review Notes For Permit 11050388 |
| Permit Number |
11050388 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-08-02 15:30:53 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SPECIFY THE SIZE OF THE DUCT SUPPLYING BEDROOM #2. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE HVAC PLANS. | | | | | | 3) THE 10" TRANSFER DUCTS FOR BEDROOMS # 1 & 2 IS TOO | | | SMALL FOR A 9" SUPPLY DUCT. A 12" TRANSFER DUCT WITH A | | | 1" DOOR UNDERCUT IS REQUIRED PER FBCR M1602.4. | | | | | | 4) SPECIFY THE SIZE OF THE RETURN GRILL IN BEDROOM #4. | | | | | | 5) PLEASE CLARIFY THE 14 X 14 GRILL AND 811 CFM SHOWN | | | AT BATH #2. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|