Plan Review Notes
Plan Review Notes For Permit 11050388
Permit Number 11050388
Review Stop P
Sequence Number 2
Notes
Date Text
2011-06-24 10:24:482007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 NOTE: THE NEW PLANS ARE FOR A COMPLETELY DIFFERENT
 DWELLING.
  
 1) THE NAME OF THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE PLUMBING SYSTEM IS REQUIRED ON THE DRAWINGS. IF
 DESIGNED BY A FLORIDA LICENSED ARCHITECT OR ENGINEER
 THE DRAWINGS ARE REQUIRED TO BE SIGNED AND SEALED AS
 REQUIRED BY FLORIDA STATUTES FS CHAPTERS 481 AND 471.
 IF DESIGNED BY A FLORIDA LICENSED PLUMBING CONTRACTOR
 UNDER EXEMPTION FS 471.003 (H), THE NAME LICENSE NUMBER
 AND SIGNATURE OF THE CONTRACTOR IS REQUIRED ON THE
 DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved