| Plan Review Notes For Permit 11050388 |
| Permit Number |
11050388 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-20 14:00:21 | | | | PLEASE REVISE THE PLAN TO INCLUDE THE FOLLOWING: | | | ADDITIONAL RECEPTACLES REQUIRED IN THE BEDROOMS AND | | | HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE | | | THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE | | | THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | PROVIDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY | | | BACKUP INSIDE AND OUTSIDE ALL SLEEPING AREAS. FBC | | | R313.2 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND | | | TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B) | | | PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOMS. NEC | | | 210.11 (C)(3) | | | VERIFY THE AVAILABLE FAULT CURRENT AT THE ELECTRIC | | | SERVICE IS LESS THAN 10,000 AIC. NEC 110.9 | | | PROVIDE ACCESS AND SAFETY CLEARANCES IN FRONT AND SIDE | | | TO SIDE AT THE ELECTRICAL PANEL BOARD. NEC 110.26 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | |
|