Plan Review Notes
Plan Review Notes For Permit 11050388
Permit Number 11050388
Review Stop E
Sequence Number 2
Notes
Date Text
2011-06-20 14:00:21 
 PLEASE REVISE THE PLAN TO INCLUDE THE FOLLOWING:
 ADDITIONAL RECEPTACLES REQUIRED IN THE BEDROOMS AND
 HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE
 THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE
 THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 PROVIDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY
 BACKUP INSIDE AND OUTSIDE ALL SLEEPING AREAS. FBC
 R313.2
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND
 TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B)
 PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOMS. NEC
 210.11 (C)(3)
 VERIFY THE AVAILABLE FAULT CURRENT AT THE ELECTRIC
 SERVICE IS LESS THAN 10,000 AIC. NEC 110.9
 PROVIDE ACCESS AND SAFETY CLEARANCES IN FRONT AND SIDE
 TO SIDE AT THE ELECTRICAL PANEL BOARD. NEC 110.26
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
  