| 2011-06-24 11:28:26 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN SHOWING THE |
| | LOCATION OF THE PROPOSED STRUCTURE ON THE LOT AND THE |
| | DISTANCES TO THE PROPERTY LINES. FBC R302.1 |
| | |
| | 2) PROVIDE TWO COPIES OF A SURFACE WATER DRAINAGE PLAN |
| | SHOWING COMPLIANCE WITH FBC R401.3. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R 403.1.4 WHICH REQUIRES |
| | ALL EXTERIOR FOOTINGS TO BE AT LEAST 12 INCHES BELOW |
| | GRADE. |
| | |
| | 4) SUBMIT TWO SETS OF ENERGY CALCULATIONS FORMS FOR THE |
| | STRUCTURE AS REQUIRED BY FBCR N1100.3. |
| | |
| | 5) PROVIDE WINDOW AND DOOR BUCK FASTENING DETAILS |
| | COMPLYING WITH FBC R613.6.1.1. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R3I3 FOR REQUIRED SMOKE |
| | ALARMS. |
| | |
| | 7) THE DESIGNER OF RECORD FOR THE STRUCTURE IS REQUIRED |
| | TO REVIEW AND APPROVE THE PRODUCT APPROVALS IN WRITING. |
| | CITY AMENDMENTS 106.3.3 |
| | |
| | 8) THE STRUCTURE IS LOCATED WITHIN 1500 FEET OF THE |
| | INTRACOASTAL WATERWAY WHICH MAKES THE EXPOSURE CATEGORY |
| | C. PLEASE CORRECT SHEET 3 AND REVISE THE REQUIRED |
| | WINDOW AND DOOR DESIGN LOADS ON SHEET 2. |
| | |
| | 9) FBC R803.2.3.1 REQUIRES ROOF SHEATHING FASTENER |
| | SPACING TO BE 6" OC IN THE FIELD AS WELL AS THE EDGES. |
| | PLEASE REVISE NOTES ON SHEET 4. |
| | |
| | 10) THE VALUE OF THE PROJECT HAS BEEN INCREASED FROM |
| | $125,000.00 TO $129,922.00 BASED ON THE CURRENT ICC |
| | VALUATION DATA TABLES. CITY AMENDMENTS 108.3 |
| | |