Plan Review Notes
Plan Review Notes For Permit 11050388
Permit Number 11050388
Review Stop P
Sequence Number 1
Notes
Date Text
2011-06-01 07:45:252007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE NAME OF THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE PLUMBING SYSTEM IS REQUIRED ON THE DRAWINGS. IF
 DESIGNED BY A FLORIDA LICENSED ARCHITECT OR ENGINEER
 THE DRAWINGS ARE REQUIRED TO BE SIGNED AND SEALED AS
 REQUIRED BY FLORIDA STATUTES FS CHAPTERS 481 AND 471.
 IF DESIGNED BY A FLORIDA LICENSED PLUMBING CONTRACTOR
 UNDER EXEMPTION FS 471.003 (H), THE NAME LICENSE NUMBER
 AND SIGNATURE OF THE CONTRACTOR IS REQUIRED ON THE
 DRAWINGS.
  
 2) THE PLANS SPECIFY A SELF VENTING KITCHEN SINK.
 PLEASE CLARIFY. DID YOU INTEND FOR THE KITCHEN SINK TO
 BE VENTED WITH AN AIR ADMITTANCE VALVE (AAV) AS ALLOWED
 BY FBCR SECTION P3114?
  
 3) PROVIDE A ROOF DRAINAGE PLAN. INDICATE THE LOCATIONS
 AND SIZES OF ALL ROOF DRAINS, SCUPPERS AND SECONDARY
 DRAINS. PROVIDE SCUPPER SIZING CALCULATIONS. FBC
 R903.4, FBC P 1105, 1106 AND 1107.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]