| Plan Review Notes For Permit 11050388 |
| Permit Number |
11050388 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-01 10:22:34 | ADDITIONAL RECEPTACLES REQUIRED IN THE ENTRANCE HALL | | | WAY, EAST HALL AND ON WEST WALL. ADD RECEPTACLES SO | | | THAT NO WALL SPACE IS MORE THAN 6 FEET FROM A | | | RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET IN | | | WIDTH HAVE A RECEPTACLE. ADDITIONAL RECEPTACLES | | | REQUIRED ON BOTH FLOORS. NEC 210.52 | | | KITCHEN RECEPTACLES SERVING THE COUNTER TOP SURFACES | | | MUST BE GFCI PROTECTED. NEC 210.8 | | | PROVIDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY | | | BACKUP INSIDE AND OUTSIDE ALL SLEEPING AREAS. FBC | | | R313.2 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND | | | TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B) | | | PROVIDE A BRANCH CIRCUIT FOR THE BATHROOMS. NEC 210.11 | | | (C)(3) | | | VERIFY THE AVAILABLE FAULT CURRENT AT THE ELECTRIC | | | SERVICE IS LESS THAN 10,000 AIC. NEC 110.9 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | | | | |
|