Plan Review Notes
Plan Review Notes For Permit 11050388
Permit Number 11050388
Review Stop E
Sequence Number 1
Notes
Date Text
2011-06-01 10:22:34ADDITIONAL RECEPTACLES REQUIRED IN THE ENTRANCE HALL
 WAY, EAST HALL AND ON WEST WALL. ADD RECEPTACLES SO
 THAT NO WALL SPACE IS MORE THAN 6 FEET FROM A
 RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET IN
 WIDTH HAVE A RECEPTACLE. ADDITIONAL RECEPTACLES
 REQUIRED ON BOTH FLOORS. NEC 210.52
 KITCHEN RECEPTACLES SERVING THE COUNTER TOP SURFACES
 MUST BE GFCI PROTECTED. NEC 210.8
 PROVIDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY
 BACKUP INSIDE AND OUTSIDE ALL SLEEPING AREAS. FBC
 R313.2
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND
 TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B)
 PROVIDE A BRANCH CIRCUIT FOR THE BATHROOMS. NEC 210.11
 (C)(3)
 VERIFY THE AVAILABLE FAULT CURRENT AT THE ELECTRIC
 SERVICE IS LESS THAN 10,000 AIC. NEC 110.9
  