| 2011-06-02 15:05:58 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN SHOWING THE |
| | LOCATION OF THE PROPOSED STRUCTURE ON THE LOT AND THE |
| | DISTANCES TO THE PROPERTY LINES. FBC R302.1 |
| | |
| | 2) PROVIDE TWO COPIES OF A SURFACE WATER DRAINAGE PLAN |
| | SHOWING COMPLIANCE WITH FBC R401.3. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R 602.1.2 (1) - (4) FOR |
| | FIRE BLOCKING. SEVERAL OF THE CROSS SECTION DRAWINGS ON |
| | THE PLANS HAVE AREAS THAT REQUIRE FIRE BLOCKING |
| | INCLUDING THE STAIRS. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A |
| | BOND BREAK BETWEEN THE REQUIRED WATER-RESISTIVE BARRIER |
| | (R703.2) AND THE STUCCO. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES |
| | DOWNSPOUTS TO DISCHARGE AT LEAST 1 FOOT AWAY FROM THE |
| | STRUCTURE. |
| | |
| | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS, WINDOWS, ROOFING MATERIAL, STORM |
| | PANELS, AND PANEL WALLS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 7) SUBMIT SHOP DRAWINGS FOR THE PANEL WALLS THAT HAVE |
| | BEEN REVIEWED AND ACCEPTED BY THE DESIGNER OF RECORD OF |
| | THE STRUCTURE. |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R312 FOR THE STAIR AND |
| | LANDING GUARD HEIGHTS AND OPENING LIMITATIONS. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION. |
| | |
| | 10) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW |
| | EACH OF THE REVIEW COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | 11) THE VALUE OF THE PROJECT HAS BEEN INCREASED FROM |
| | $125,000.00 TO $274,638.00 BASED ON THE CURRENT ICC |
| | VALUATION DATA TABLES. CITY AMENDMENTS 108.3 |
| | |