2011-06-07 10:53:012007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SHEET NUMBER 4 OF THE PLANS HAS THE WRONG CODE
 INFORMATION. THE CORRECT CODE IS THE 2007 FBC WITH 2009
 AMENDMENTS, ASCE 7-05 AND THE EXPOSURE CATEGORY IS 'C'.
 FBC 301.2.1.1
  
 2) PROVIDE STRUCTURAL DETAILS FOR THE ARCHES AT THE
 OPENINGS ON THE PORCH. FBC 601.2
  
 3) SPECIFY THE TRUSS SPACING ON THE ROOF FRAMING PLANS.
 FBC R802.1.6.1
  
 4) SPECIFY THE ROOF OVERHANG ON THE PLANS. FBC R320.7
  
 5) SPECIFY THE ROOF DECK MATERIAL AND THICKNESS. FBC
 R803.2.2
  
 6) SPECIFY THE ATTACHMENT OF THE LINTELS AT EACH SIDE
 OF THE PORCH TO THE EXISTING STRUCTURE. FBC R606.1 AND
 CITY AMENDMENTS 106.1.2
  
 7) SPECIFY THE METHOD OF ATTACHMENT FROM THE PRODUCT
 APPROVAL THAT WILL BE USED TO INSTALL THE CONCRETE ROOF
 TILE AND PROVIDE ADEQUATE ATTACHMENT RESISTANCE. DCA
 RULE 9N-3 AND FBC R905.3.7
  
 8) THE GLASS BLOCK INSTALLATION DOES NOT COMPLY WITH
 THE PARAMETERS OF THE PRODUCT APPROVAL. THE MAXIMUM
 HEIGHT IS 8 FEET AND THE MAXIMUM WIDTH IS 4 FEET. A 2
 PIECE ALUMINUM CHANNEL AROUND THE PERIMETER ATTACHED TO
 MASONRY/CONCRETE WITH CONCRETE SCREWS AT 12 INCHES ON
 CENTER IS REQUIRED PER THE NOA. DCA RULE 9N-3 AND FBC
 R301.1
  