Plan Review Notes
Plan Review Notes For Permit 11050338
Permit Number 11050338
Review Stop E
Sequence Number 1
Notes
Date Text
2011-05-13 08:46:202007 FBC W/2009 REVISIONS
 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) REVISE LOAD CALCULATIONS AND PANEL SCHEDULE TO
 INCLUDE THE THIRD AHU HEAT STRIP AND A/C COMPRESSOR.
 NEC 220.40
  
 2) REVISE THE ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION
 NOTE ON SHEET C-1. NEC 210.12 REQUIRES ARC-FAULT
 PROTECTION ON ALL 120-VOLT, SINGLE PHASE 15 AND 20 AMP
 BRANCH CIRCUITS SUPPLYING OUTLETS DWELLING UNITS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW