| Plan Review Notes For Permit 11050338 |
| Permit Number |
11050338 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-13 08:46:20 | 2007 FBC W/2009 REVISIONS | | | 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) REVISE LOAD CALCULATIONS AND PANEL SCHEDULE TO | | | INCLUDE THE THIRD AHU HEAT STRIP AND A/C COMPRESSOR. | | | NEC 220.40 | | | | | | 2) REVISE THE ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION | | | NOTE ON SHEET C-1. NEC 210.12 REQUIRES ARC-FAULT | | | PROTECTION ON ALL 120-VOLT, SINGLE PHASE 15 AND 20 AMP | | | BRANCH CIRCUITS SUPPLYING OUTLETS DWELLING UNITS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|