| Plan Review Notes For Permit 11050309 |
| Permit Number |
11050309 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-10-26 09:56:43 | ONLY ONE SET OF PLANS REVISED. TWO SETS OF REVISIONS | | | FOR THE ELECTRICAL PLAN ARE REQUIRED. | | | ELECTRICAL FEEDER WITH OVERCURRENT PROTECTION TO NEW | | | PANEL IN GARAGE NOT SPECIFIED. MIN. #3 FEEDERS WITH # 8 | | | GROUND REQUIRED FOR A 100 AMPERE SUB PANEL. SMOKE | | | DETECTORS REQUIRED IN ALL BEDROOMS. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | | |
|