| Plan Review Notes For Permit 11050309 |
| Permit Number |
11050309 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-25 09:56:06 | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY | | | BACK UP. HOMES WHICH FEATURE GAS APPLIANCES, AN | | | ATTACHED GARAGE OR A FIRE PLACE REQUIRE A CARBON | | | MONOXIDE DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR | | | SLEEPING. FBC R313 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | NEW RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED. | | | NEC 210-12 (B) | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES 2 FEET OR | | | MORE IN WIDTH HAVE A RECEPTACLE. NEDC 210.52 | | | THE PLAN SHOWS MULTIPLE ELECTRIC CIRCUITS FEEDING THE | | | GARAGE. A SEPARATE DISCONNECT AND PANELBOARD IS | | | REQUIRED. NEC 225-30 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|