| Plan Review Notes For Permit 11050304 |
| Permit Number |
11050304 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-12-02 12:49:02 | 1225 PALM BEACH LAKES BOULEVARD | | | PERMIT #11050304 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE OCCUPANT LOAD OF 94 ON SHEET A0 DOES NOT MATCH THE | | | INDIVIDUAL ROOM OCCUPANT LOADS PROVIDED ON SHEET A1. | | | | | | EXIT ACCESS CORRIDORS SHALL PROVIDE DIRECT ACCESS TO | | | EXITS WITHOUT PASSING THROUGH INTERVENING ROOMS. | | | | | | THE NORTHWEST CORRIDOR HAS A DEAD-END EXCEEDING 20 FEET | | | OF TRAVEL. | | | | | | SHEET LS1 INDICATES A MIXED USE OCCUPANCY OF EDUCATION | | | AND DAY CARE. EDUCATIONAL OCCUPANCIES REQUIRE 6 FEET | | | WIDE EXIT ACCESS CORRIDORS. | | | | | | PROVIDE MECHANICAL PLAN SHOWING ALL DUCT SMOKE | | | DETECTORS AND FIRE DAMPERS. | | | | | | FIRE ALARM CONSTRUCTION DOCUMENTS WERE NOT SUBMITTED | | | WITH THE DESIGN DRAWINGS. | | | | | | A COMPLETE SMOKE DETECTION SYSTEM SHALL BE INTEGRATED | | | WITH THE FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|