| 2011-12-27 09:28:56 | BUILDING PLAN REVIEW |
| | PERMIT: 11050304 |
| | ADD: 1225 PALM BEACH LAKES BLVD |
| | CONT: CILAS CONCRETE CONSTRUCTION |
| | TEL: (561)252-8429 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B |
| | 106.3.5.1.1: |
| | 2A)COMPLIED. |
| | 2B) COMPLIED- BUILDING NOT SPRIVKLERED. |
| | 2C) COMPLIED. |
| | 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS |
| | INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS |
| | PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND |
| | INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL |
| | LOAD. |
| | 12/27/2011 PLANS INDICATE AN OCCUPANT LOAD BASED ON 36 |
| | SQ FT / OCCUPANT PLEASE REVIEW TABLE 1004.1.1 DAYCARE |
| | 20/ NET |
| | |
| | 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, |
| | MISSING REPORTS ARE AS FOLLOWS: |
| | |
| | 3A) NEW EXTERIOR DOOR. PLEASE REVIEW REQUIREMENTS FOR: |
| | 1034.1 PANIC AND FIRE EXIT HARDWARE. |
| | 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK |
| | ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE |
| | WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS |
| | (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE |
| | DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE |
| | BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE |
| | WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR |
| | THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864 |
| | MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR. |
| | WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR, |
| | THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT |
| | HARDWARE. |
| | |
| | 3B) NEW- EGRESS WINDOWS |
| | |
| | 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE |
| | HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE |
| | PLAN. |
| | |
| | 5-9) COMPLIED. |
| | |
| | 10) NO PRODUCT APPROVAL FOR THE NEW WINDOWS IN |
| | CLASSROOMS COMPLYING WITH :2007/09 FBC-B 1026.4.1 EVERY |
| | ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2 M2) IN |
| | EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR OTHER |
| | EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO STUDENT |
| | OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY SUBJECT TO |
| | CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN GROUP D |
| | OCCUPANCIES SHALL HAVE NOT LESS THAN ONE OUTSIDE WINDOW |
| | FOR EMERGENCY RESCUE THAT COMPLIES WITH THE FOLLOWING: |
| | |
| | 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH, |
| | 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53 |
| | M2) IN AREA. |
| | |
| | 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING |
| | DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE |
| | THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR |
| | FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE |
| | SHALL BE READILY ACCESSIBLE TO THE STAFF. |
| | |
| | 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE |
| | NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY |
| | WITH SECTION 715.3. |
| | |
| | |
| | 14) NOT REQUIRED NO LAUNDRY! |
| | |
| | 15) NORTHWEST CORRIDOR MARKED AS "NO EXIT WHICH CREATES |
| | A DEAD-END CORRIDOR OVER 20'-0" LONG. FBC-B 1017.3. |
| | DEAD END CORRIDOR CAN'T BE OVER 20'-0" IN LENGTH. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |