| 2011-10-25 13:26:51 | 1225 PALM BEACH LAKES BOULEVARD |
| | PERMIT #11050304 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER |
| | FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| | 69A-60.0081. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | DIRECTING OCCUPANTS TO EXIT THROUGH A STORAGE AREA IS |
| | NOT PERMITTED. |
| | |
| | WALL DETAIL THREE DOES NOT APPEAR TO PROVIDE A ONE-HOUR |
| | FIRE RATING. |
| | |
| | PROVIDE A DOOR AND HARDWARE SCHEDULE. |
| | |
| | EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN |
| | OPEN THE DOOR FROM INSIDE THE CLOSET. |
| | |
| | EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW |
| | OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY STAFF |
| | MEMBERS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE CARBON MONOXIDE DETECTORS FOR GAS FUELED |
| | APPLIANCES/WATER HEATERS. |
| | |
| | ELECTRICAL RECEPTACLES SHALL BE PROVIDED WITH |
| | PROTECTIVE COVERS. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT (50 PERCENT IF FULLY |
| | SPRINKLERED) OF THE INDIVIDUAL WALL AREA. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. |
| | |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | A SMOKE DETECTION SYSTEM IS REQUIRED IN DAY-CARE |
| | OCCUPANCIES. CARBON MONOXIDE DETECTORS WILL ALSO BE |
| | REQUIRED IN SLEEPING AREAS IF THE BUILDING USES GAS |
| | WATER HEATERS OR GAS APPLIANCES. |
| | |
| | SHEET LS1 INDICATES THE BUILDING IS PROTECTED BY |
| | EXISTING FIRE ALARM AND FIRE SPRINKLER SYSTEMS. |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED TO SHOW THE SCOPE |
| | OF WORK AFFECTING THESE EXISTING SYSTEMS. FIRE ALARM |
| | SYSTEM SHALL BE CERTIFIED FOR CENTRAL STATION SERVICE. |
| | |
| | VERIFY FIRE SPRINKLER SYSTEM EXISTS AS THIS WILL AFFECT |
| | THE REQUIREMENT FOR RESCUE WINDOWS OR OTHER EXITS. |
| | |
| | SEPARATE PLANS AND SUB-PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |