| 2011-11-03 10:23:11 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE ENGINEERED DETAIL FOR ATTACMENT OF NEW |
| | ROOFTOP EQUIPMENT TO BUILDING STRUCTURE PER FBC-M |
| | 301.12. |
| | |
| | 2. PAGE M-1 OUTSIDE AIR CALCULATION: TABLE INDICATES |
| | CALCULATIONS ARE PER FBC-M 403.3 WHILE NOTE #2 |
| | INDICATES ASHRAE 62.1 IS USED. WHICH IS CORRECT? ONE |
| | METHOD OR THE OTHER SHALL BE LECTED AND ADHERED TO. |
| | |
| | 3. PAGE M-1 OUTSIDE AIR CALCULATION: IF ASHRAE 62.1 IS |
| | ELECTED, THE VENTILATION TOTALS LISTED ARE TO ALSO |
| | INCLUDE AN ADDITIONAL 0.18 CFM/SF OF FLOOR AREA IN THE |
| | SPACES BEING VENTILATED FOR DAYCARE OCCUPANCIES. SEE |
| | ASHRAE 62.1 TABLE 6-1 AND BREATHING ZONE OUTDOOR |
| | AIRFLOW EQUATION 6-1 IN SECTION 6.2.2.1. |
| | |
| | 4. PLANS INDICATE HVAC SYSTEM DESIGN BY "K.O. ENERGY |
| | DESIGN, LLC." THIS DOES NOT APPEAR TO BE A PROFESSIONAL |
| | ENGINEER OR ENGINEERING BUSINESS. PLANS MUST BE |
| | DESIGNED BY AN ENGINEER IN ACCORDANCE WITH FBC-B |
| | 105.3.1.2. SYSTEM MAY NOT BE DESIGNED BY A CONTRACTOR |
| | BECAUSE THE BUILDING OCCUPANT LOAD EXCEEDS 100 PERSONS. |
| | WHILE PAGE M-1 IS SIGNED AND SEALED BY AN ENGINEER, THE |
| | ENGINEER IS A "STRUCTURAL ENGINEER" AND NOT TAKING |
| | RESPONSIBILITY FOR THE MECHANICAL DESIGN. |
| | |