Plan Review Notes
Plan Review Notes For Permit 11050228
Permit Number 11050228
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-05-26 17:02:378989 OKEECHOBEE BOULEVARD
 PERMIT #11050228
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-1 ENTRANCE VESTIBULE 101 IS NOT WIDE ENOUGH TO
 ACCOMMODATE THE TWO MERGING OCCUPANT LOADS TOTALING
 1050 PERSONS. POWERED CARTS AND VENDING MACHINES ARE
 RESTRICTING REQUIRED EGRESS WIDTH.
  
 SHEET SP-1 INDICATE LOCATION OF CONSTRUCTION TRAILERS,
 MATERIALS AND EQUIPMENT STAGING AREA, TEMPORARY FENCES,
 FIRE HYDRANTS ETC. IF APPLICABLE.
  
 SHEET D-1 ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. FIRE PROTECTION SYSTEMS SHALL
 REMAIN ACTIVE DURING DEMOLITION AND RENOVATION
 ACTIVITIES. IN THE EVENT A FIRE PROTECTION SYSTEM IS
 OUT OF SERVICE FOR MORE THAN 4-HOURS IN A 24-HOUR
 PERIOD, THE BUILDING SHALL BE PLACED UNDER A FIRE
 WATCH. ALL FIRE WATCH REQUESTS MUST BE APPROVED AND
 SUBMITTED IN WRITING TO THE OFFICE OF THE FIRE MARSHAL.
  
 SHEET FP-1 INDICATE THE HAZARD CLASSIFICATION AND
 DENSITY FOR THE NEW SPACES. THE SCOPE OF SPRINKLER WORK
 APPEARS MINIMAL COMPARED TO THE EXTENSIVE CEILING WORK
 SHOWN ON SHEET A-2.
  
 SHEET FA-1 AND FA-2 ARE SIGNED BUT NOT SEALED BY THE
 ENGINEER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW