| 2011-06-08 12:19:05 | BUILDING PLAN REVIEW |
| | PERMIT: 11050228 |
| | ADD: 8989 OKEECHOBEE BLVD |
| | CONT: D& J CONSTRUCTION |
| | TEL: (954)587-2360 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODEW/ 2009 FBC |
| | SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | BUILDING PROVISO: |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET S-2 DETAIL #1: |
| | 1A) PLANS INDICATE THE USE OF PLYWOOD SHEATHING TO |
| | INFILE OLD ROOF HATCH LOCATION. PLANS INDICATE TO |
| | SECURE PLYWOOD TO STEEL WITH WOOD ADHESIVE, PLEASE |
| | PROVIDE ENGINEERING FOR COMPLIANCE TO THE 140 MPH WIND |
| | ZONE. 2007/09 FBC-B 1609. |
| | |
| | 1B) SAME DETAIL INDICATES TO INFILL THE HOLE LEFT FROM |
| | THE OLD ROOFHATCH LOCATION WITH 3/4 INCH PLYWOOD |
| | SHEATHING. THE ORIGINAL BUILDING WAS DESIGNED UNDER THE |
| | 1994 SBC , BUILDING TYPE IV WHICH IS EQUAL TO A |
| | BUILDING TYPE IIB 2007/09 FBC-B. PLEASE REVIEW SECTION |
| | 603.1.3 FIRE RETARDANT TREATED WOOD SHALL BE INSTALLED. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |