| Plan Review Notes For Permit 11050149 |
| Permit Number |
11050149 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-09 11:45:38 | RESIDENTIAL (R3) DOOR REPLACEMENT BUILDING REVIEW | | | CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- DESIGN PRESSURES SHOWN ON THE FLORIDA PRODUCT | | | APPROVAL FL11321.1 SUBMITTED DON'T MEET THE CALCULATED | | | DESIGN PRESSURES. NEED TO PROVIDE PRODUCT APPROVAL FOR | | | DOOR THAT MEETS THE CALCULATED DESIGN PRESSURES. | | | | | | 2- SIZE OF DOOR SHOWN ON THE PRODUCT APPROVAL IS FOR A | | | 6'-8" HIGH DOOR. CALCULATIONS SUBMITTED SHOW AN 8'-0" | | | HIGH DOOR. PROVIDE PRODUCT APPROVAL FOR SIZE DOOR SHOWN | | | ON THE CALCULATIONS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|