Plan Review Notes
Plan Review Notes For Permit 11050110
Permit Number 11050110
Review Stop P
Sequence Number 1
Notes
Date Text
2011-06-01 09:57:42FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET A-2 LISTS OCCUPANCY AS A3, OCCUPANT LOAD AS
 662. PER 403.3 . FOR 331 WOMEN 5 WC WILL BE REQUIRED.
 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED
 WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS
 SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON
 THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT
 OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE
 SEXES
  
 2. A UNISEX TOILET ROOM WILL BE REQUIRED. FIXTURES
 LOCATED IN THE UNISEX TOILET ROOM COUNT AS PART OF THE
 FIXTURE COUNT.
 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY AND
 MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET
 ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED. IN
 BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE WATER CLOSETS
 REQUIRED FOR THE ASSEMBLY OR MERCANTILE OCCUPANCY SHALL
 BE USED TO DETERMINE THE UNISEX TOILET ROOM
 REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  