| 2011-05-18 12:41:45 | 540 CHEERFUL STREET |
| | PERMIT NUMBER 11050110 |
| | MULTI-PURPOSE ADDITION |
| | |
| | 1. SITE PLAN DOES NOT ILLUSTRATE ANY NEW OR EXISTING |
| | FIRE HYDRANTS. |
| | |
| | 2. PLEASE INDICATE ON THE LIFE SAFETY FLOOR PLAN SHEET |
| | A-2 WHERE THE PHYSICALLY CHALLENGED ARE SEATED IN THE |
| | PROPOSED MULTI-PURPOSE AREA. |
| | |
| | 3. THE BUILDING WILL NEED TO BE IDENTIFIED WITH A |
| | MALTESE CROSS THAT CONTAINS AN R IN THE CENTER |
| | SIGNIFYING THAT A WOODEN ROOF TRUSS IS PRESENT. |
| | (ALDRIDGE / BENGE FIRE SAFETY RULE FOR IDENTIFYING ROOF |
| | AND FLOOR TRUSSES) |
| | |
| | 4. NO EMERGENCY LIGHTS DISPLAYED ON SHEET E-1. |
| | |
| | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR AUTOMATIC |
| | FIRE SPRINKLER SYSTEM. FIRE SPRINKLER SYSTEM PLANS |
| | REQUIRED WITH THE ADDITION PLANS TO DETERMINE GENERAL |
| | LAYOUT AND SYSTEM DESIGN CRITERIA. |
| | |
| | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | ALARM SYSTEM EQUIPMENT. |
| | |
| | 7. THE FIRE ALARM AND FIRE SPRINKLER SYSTEM IS TO BE |
| | MONITORED BY AN APPROVED THIRD PARTY CAPABLE OF |
| | PROVIDING CENTRAL STATION SERVICE. |
| | |
| | 8. CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. |
| | |
| | 9. EXITS ARE TO BE PROPERLY MAINTAINED DURING |
| | CONSTRUCTION. |
| | |
| | 10. CARE IS TO BE USED WHEN USING ANY GASOLINE POWERED |
| | SAWS INDOORS. CARBON MONOXIDE (CO) IS A COLORLESS, |
| | ODORLESS, AND TASTELESS GAS AND IN THE RIGHT |
| | CONCENTRATION CAN BE FLAMMABLE. PROPER VENTILATION |
| | CONTROLS ARE TO BE PROVIDED TO PREVENT THE BUILD-UP OF |
| | CARBON MONOXIDE VAPORS. |
| | |
| | 11. A KNOX BOX WILL BE REQUIRED FOR THIS LOCATION. KNOX |
| | BOXES CAN BE ORDERED AT WWW.KNOXBOX.COM. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |