Plan Review Notes
Plan Review Notes For Permit 11050110
Permit Number 11050110
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-05-18 12:41:45540 CHEERFUL STREET
 PERMIT NUMBER 11050110
 MULTI-PURPOSE ADDITION
  
 1. SITE PLAN DOES NOT ILLUSTRATE ANY NEW OR EXISTING
 FIRE HYDRANTS.
  
 2. PLEASE INDICATE ON THE LIFE SAFETY FLOOR PLAN SHEET
 A-2 WHERE THE PHYSICALLY CHALLENGED ARE SEATED IN THE
 PROPOSED MULTI-PURPOSE AREA.
  
 3. THE BUILDING WILL NEED TO BE IDENTIFIED WITH A
 MALTESE CROSS THAT CONTAINS AN R IN THE CENTER
 SIGNIFYING THAT A WOODEN ROOF TRUSS IS PRESENT.
 (ALDRIDGE / BENGE FIRE SAFETY RULE FOR IDENTIFYING ROOF
 AND FLOOR TRUSSES)
  
 4. NO EMERGENCY LIGHTS DISPLAYED ON SHEET E-1.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR AUTOMATIC
 FIRE SPRINKLER SYSTEM. FIRE SPRINKLER SYSTEM PLANS
 REQUIRED WITH THE ADDITION PLANS TO DETERMINE GENERAL
 LAYOUT AND SYSTEM DESIGN CRITERIA.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM EQUIPMENT.
  
 7. THE FIRE ALARM AND FIRE SPRINKLER SYSTEM IS TO BE
 MONITORED BY AN APPROVED THIRD PARTY CAPABLE OF
 PROVIDING CENTRAL STATION SERVICE.
  
 8. CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 9. EXITS ARE TO BE PROPERLY MAINTAINED DURING
 CONSTRUCTION.
  
 10. CARE IS TO BE USED WHEN USING ANY GASOLINE POWERED
 SAWS INDOORS. CARBON MONOXIDE (CO) IS A COLORLESS,
 ODORLESS, AND TASTELESS GAS AND IN THE RIGHT
 CONCENTRATION CAN BE FLAMMABLE. PROPER VENTILATION
 CONTROLS ARE TO BE PROVIDED TO PREVENT THE BUILD-UP OF
 CARBON MONOXIDE VAPORS.
  
 11. A KNOX BOX WILL BE REQUIRED FOR THIS LOCATION. KNOX
 BOXES CAN BE ORDERED AT WWW.KNOXBOX.COM.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION