Plan Review Notes
Plan Review Notes For Permit 11050110
Permit Number 11050110
Review Stop E
Sequence Number 1
Notes
Date Text
2011-05-31 11:55:55PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS
 3412.ABC.1.3
 PROVIDE A LOAD CALCULATION AND PROPOSED PANEL SCHEDULE
 SHOWING ALL LOADS FOR THE EXISTING MAIN ELECTRICAL
 PANEL. NEC 215.5
 THE # 3 FEEDERS TO THE NEW SUB PANEL REQUIRE
 OVERCURRENT PROTECTION. NEC T. 310.16
 A GFCI PROTECTED RECEPTACLE IS REQUIRED TO SERVICE THE
 MECHANICAL EQUIPMENT (ACU). NEC 210.63
 PROVIDE EMERGENCY EGRESS LIGHTING. FBC 1006.1
 PROVIDE ILLUMINATED EXIT SIGNS. FBC 1006.3
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  