2011-05-20 14:17:41BUILDING PLAN REVIEW
 PERMIT: 11050110
 ADD: 540 CHEERFULL ST.
 CONT: WINGATE CORP LLC
 TEL: (561)718-5133
  
 2007 FLORIDA BUILDING CODE W/ 2009 SUPPLEMENTS
 2007 FL EXISTING BLDG CODE W/ 2009 SUPPLEMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-2 INDICATES A TOTAL OCCUPANT LOAD OF 662,
 THIS ADDITION WILL CLASSIFY THIS BUILDING AS A
 THRESHOLD BUILDING UNDER FL S 553.71 (7).
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 1C) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 1C)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 1C)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED
 BY ALL CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING
 OFFICIAL OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER
 THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1D) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 NOTE: A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE
 ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD.
  
 2) SHEET A-2 BUILDING CODE ANALYSIS INDICATES THIS
 BUILDING IS TO BE DESIGNED TO A BUILDING TYPE IIB.
 PLEASE NOTE THE MINIMUM CODE REQUIRED BUILDING TYPE
 WOULD BE A VB WITH THE AREA INCREASES & FIRE SPRINKLER
 INCREASE WE WOULD BE WELL OVER THE REQUIRED MINIMUMS OF
 THE CODE. BUILDING THIS STRUCTURE AS A TYPE IIB
 STRUCTURE PLEASE BE AWARE OF THE ROOF ASSEMBLY AND ROOF
 SHEATHING LIMITATIONS. PLEASE REVIEW 2007/09 FBC-B
 SECTION
 603.1.3. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED
 IN: 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING. THIS WOULD MEAN ALL NEW MATERIALS
 AS WELL AS THE EXISTING ROOF FRAMING AND SHEATHING
 WOULD NEED TO MEET THE FIRE RESISTANT- TREATED
 MATERIALS.
  
 3A) SHEET A-1 NOTE #19 INDICATES THE REMOVAL OF BLOCK
 WALLS WHICH APPEAR TO BE EXTERIOR BEARING WALLS WITH NO
 ADDITIONAL STRUCTURAL SUPPORT OF THE EXISTING BEAMS.
 NORMALLY THIS WOULD HAVE BEEN A 4 BAR SYSTEM NO HOOPS
 SINCE THERE WAS BLOCK WORK BELOW. SHEET A-5 INDICATES
 THE NEW PIGGYBACK TRUSSES, SHEATHING AND ROOFING
 ASSEMBLIES WILL BE ADDING ADDITIONAL LOADING TO THE
 BEAM THAT WAS NOT DESIGNED FOR FREE SPANS.
 PLEASE REVIEW SECTION:
 2007/09 EXISTING BLDG CODE 1003.2 ADDITIONAL GRAVITY
 LOADS. EXISTING STRUCTURAL ELEMENTS SUPPORTING ANY
 ADDITIONAL GRAVITY LOADS AS A RESULT OF ADDITIONS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING .
 EXCEPTION: 1. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT
 INCREASED BY MORE THAN 5 PERCENT.
 PLANS INDICATE THE USE OF C-CHANNEL PN-39 & PN-58. THE
 PLANS ALSO INDICATE A DETAIL# 02/A-4 A END DETAIL FOR
 THE SOUTH END, SHEET A-3 THE NORTH END INDICATES WHAT
 APPEARS TO BE A NEW FOOTING BUT NO DETAILS HOW TO TAKE
 THE LOADING OF THE PAIR OF C-CHANNELS PN-39. WILL THER
 BE SHOP DRAWINGS INDICATING WHERE THE SPLICES WILL
 OCURR IN THE C-CHANNEL?
  
 3B) THE 2ND CONCERN WOULD BE THE ADDITIONAL LOAD THE
 PIGGYBACK TRUSSES ARE TTRANSFERRING TO THE ORIGINAL
 TRUSSES IN SOME CASES THE ORIGINAL TRUSSES AARE
 CARRYING ANYWHERE FROM 25-50 % OF THE DEAD LOAD OF THE
 NEW TRUSSES, PLEASE PROVIDE A STRUCTURAL ANALYSIS OF
 THTE EXISTING TRUSSES TO CARRY THIS ADDITIONAL LOADING.
 2007/09 EXISTING BLDG CODE 1003.2 ADDITIONAL GRAVITY
 LOADS. EXISTING STRUCTURAL ELEMENTS SUPPORTING ANY
 ADDITIONAL GRAVITY LOADS AS A RESULT OF ADDITIONS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING .
 EXCEPTION: 1. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT
 INCREASED BY MORE THAN 5 PERCENT.
  
 4) SHEET A-1, NOTE EN #17, INDICATES THE REMOVAL OF
 WINDOWS IN THE EXISTING EXTERIOR WALL AND
 REINSTALLATION IN THE NEW EXTERIOR WALLS OF THE
 ADDITION. TO REUSE THESE WINDOWS WITHIN THE ADDITION
 THEY MUST MEET THE STANDARD FOR NEW CONSTRUCTION IN THE
 FBC-B. FLORIDA EXISTING BUILDING CODE 1003.1 COMPLIANCE
 WITH THE FLORIDA BUILDING CODE. ADDITIONS TO EXISTING
 BUILDINGS OR STRUCTURES ARE NEW CONSTRUCTION AND SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING.
 PROVIDE DOCUMENTATION FOR LARGE MISSILE IMPACT
 RESISTANT TESTING FBC-B 1609.1.2 AND FOR FBC-B
 1714.5.1. DESIGN PRESSURES.
  
 5) SHEET A-2 BUILDING CODE ANALYSIS, PLEASE REVIEW WIND
 DESIN CRITERIA, SPECIFICLLY THE IMPORTANCE FACTOR OF
 1.0. PLEASE REVIEW 2007 FBC-B TABLE 1604.5 OCCUPANCY
 CATEGORY III AND NATURE OF OCCUPANCY & TTHE CODE
 COMMENTARY. THE CODE COMENTARY LIST THE ASSEMBLY
 OCCUPANCY GREATER THAN 300 OCCUPANTS AS A TYPE III
 OCCUPANCY CATEGORY WILL HAVE AN IMPORTANCE FACTOR III
 WHICH TRANSLATES INTO 1.15 IN HURRICANE PRONE REGIONS
 WITH
 V > 100 MPH. THIS WILL EFFECT ALL PRESSURES ON THE MAIN
 FORCE RESISTING SYSTEM AS WELL AS COMPONENTS AND
 CLADDING, AN ANALYSIS WILL ALSO NEED TO BE
 COMPLETED FOR THE ORIGINAL BUILDING.
  
 6) PLEASE PROVIDE COMPLIANCE WITH: 2007/09 FBC-B [F]
 907.2.1 GROUP A. A MANUAL FIRE ALARM SYSTEM SHALL BE
 INSTALLED IN GROUP A OCCUPANCIES HAVING AN OCCUPANT
 LOAD OF 300 OR MORE.
 EXCEPTION: MANUAL FIRE ALARM BOXES ARE NOT REQUIRED
 WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM AND THE ALARM NOTIFICATION
 APPLIANCES WILL ACTIVATE UPON SPRINKLER WATER FLOW.
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 3 (THRESHOLD INSPECTOR) COPIES OF PRODUCT
 TESTING REPORTS FOR THE MISSING REPORTS ARE AS FOLLOWS:
 7A) WINDOWS
 7B) EXTERIOR DOORS
 7C) LINTELS
 7D) WALL LOUVER A/C MAKE UP AIR
 7E) ROOFING ASSEMBLIES
  
 8) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved