Plan Review Notes
Plan Review Notes For Permit 11050095
Permit Number 11050095
Review Stop B
Sequence Number 2
Notes
Date Text
2011-08-05 10:52:48BUILDING PLAN REVIEW
 PERMIT: 11050095
 ADD: 301 N OLIVE AVE 6TH / 12TH FLOOR
 CONT: E H PASCHER
 TEL: (954)261-5726
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 ON THE PERMIT APPLICATION UNDER THE HEADING DESCRIBE
 PROJECT IN DETAIL , PART OF THE DESCRIPTION INDICATES
 REPLACE ROOF TOP FANS ON THE 6TH AND 12 FLOOR.
 PRODUCT APPROVAL SUBMITTED IS :
  
 NOA# 09-0511.03 GREENHECK MODEL FG1, FG3 & R -SERIES
 STEEL/ ALUMINUM ROOF FANS , MODEL NOT IDENTIFIED AS TO
 SIZE, STANDARD OR FILTERED NOR TYPE OF MATERIALS +/-
 130 PSF STEEL & ALUMINUM +/- 70.
  
 SHEET M 6.1 DETAIL FOR GRAVITY VENT DOES NOT INDICATE
 TYPE OF MATERIAL TO BE USED ON THE SHELL OF THE FAN.
 SHEET M5.0 GRAVITY ROOF VENTILATOR NOTE 2 HOUSING TO BE
 ALUMINUM WITH 13INCH BASE HEIGHT (MAXIMUM). DESIGNER OF
 RECORD VERIFICATION THAT THE GREENHECK MODEL FG1, FG3 &
 R ALUMINUM SERIES VENTILATOR MEET THE WIND PRESSURES
 FOR THE LOCATIONS ON THE 6TH AND 12TH FLOOR ROOF
 LEVELS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  