Notes
Date Text
2011-05-10 12:17:38BUILDING PLAN REVIEW
 PERMIT: 11050095
 ADD: 301 N OLIVE AVE 6TH / 12TH FLOOR
 CONT: E H PASCHER
 TEL: (954)261-5726
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ON THE PERMIT APPLICATION UNDER THE HEADING DESCRIBE
 PROJECT IN DETAIL , PAT OF THE DESCRIPTION INDICATES
 REPLACE DOORS ON TTHE 6TH AND 12 FLOOR.
 PRODUCT APPROVALS SUBMITTED ARE :
  
 NOA# 06-0612.03 DAYBAR INDUSTRIES LIMITED SERIES LS 18,
 FLUSH OUTSWING COMMERCIAL STEEL DOOR =/- 60 PSF.
  
 NOA# 09-0511.03 GREENHECK MODEL FG1, FG3 & R -SERIES
 STEEL/ ALUMINUM ROOF FANS , MODEL NOT IDENTIFIED AS TO
 SIZE, STANDARD OR FILTERED NOR TYPE OF MATERIALS +/-
 130 PSF STEEL & ALUMINUM +/- 70.
  
 NOA# 10-0921.09 GREENHECK MODEL ESD-635 D ALUMINUM
 LOUVER W/ WITHOUT VCD-40 DAMPER +/- 150 PSF.
  
 1A) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1B) THE REPLACEMENT OF DOORS, EXHAUST FANS AND LOUVERS
 ON A HIGH RISE BUILDING REQUIRES ENGINEERING AAS TO
 WIND DESIN CRITERIA AS TO ASCE 7-05. NO LOCATIONS HAVE
 BEEN PROVIDED IF THESE UNITS DOORS LOUVERS ARE LOCATED
 IN AN INTERIOR ZONE OR END ZONE. THE SAME HOLDS TRUE
 FOR THE ROOF FAN, THE LOCATION IS UNKNOWNED PLEASE
 PROVIDE LOCATION TO BE LOCATED WITHIN ROOF ZONE 1,2 OR
 3. 2007/09 FBC-B 1609. COMPONENTS & CLADDING.
  
 1C) 1609.6.2 WIND DESIGN PROCEDURES
 1C)1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1C)2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1C)3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 1C)4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1C)5) POSITIVE / NEGATIVE PRESSURES.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  