| Plan Review Notes For Permit 11050090 |
| Permit Number |
11050090 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-05 11:49:45 | 1300 ALLENDALE ROAD | | | PERMIT #11050090 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | VERIFY SPRINKLER SYSTEM BACKFLOW PREVENTER VALVES ARE | | | SUPERVISED BY THE FIRE ALARM SYSTEM. | | | | | | PROVIDE ROOM IDENTIFICATION ON PLANS. | | | | | | THE WAREHOUSE LOCATION OF NOTIFICATION APPLIANCES | | | LABLED AS CEILING MOUNTED APPEAR TO BE WALL MOUNTED. | | | IDENTIFY THE CEILING HEIGHTS. | | | | | | NO MANUAL PULL STATION SHOWN FOR DOOR NEAR NOTIFICATION | | | APPLIANCE A2-7. | | | | | | PROVIDE POINT TO POINT WIRE CONNECTIONS ON FLOOR PLAN. | | | | | | SEVERAL ROOMS AND CORRIDORS APPEAR TO REQUIRE | | | ADDITIONAL NOTIFICATION APPLIANCE COVERAGE SUCH AS | | | A3-3, A4-1, A4-2, B1-2, B2-4, ETC. | | | | | | NO NOTIFICATION HAS BEEN PROVIDED FOR THE MEZZANINE OR | | | FOR THE CORRIDOR EAST OF APPLIANCE B1-1 OR NORTH OFFICE | | | ENTRANCE NEAR PULL STATION M6. | | | | | | DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM CONDITION. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|