2011-05-05 11:49:451300 ALLENDALE ROAD
 PERMIT #11050090
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 VERIFY SPRINKLER SYSTEM BACKFLOW PREVENTER VALVES ARE
 SUPERVISED BY THE FIRE ALARM SYSTEM.
  
 PROVIDE ROOM IDENTIFICATION ON PLANS.
  
 THE WAREHOUSE LOCATION OF NOTIFICATION APPLIANCES
 LABLED AS CEILING MOUNTED APPEAR TO BE WALL MOUNTED.
 IDENTIFY THE CEILING HEIGHTS.
  
 NO MANUAL PULL STATION SHOWN FOR DOOR NEAR NOTIFICATION
 APPLIANCE A2-7.
  
 PROVIDE POINT TO POINT WIRE CONNECTIONS ON FLOOR PLAN.
  
 SEVERAL ROOMS AND CORRIDORS APPEAR TO REQUIRE
 ADDITIONAL NOTIFICATION APPLIANCE COVERAGE SUCH AS
 A3-3, A4-1, A4-2, B1-2, B2-4, ETC.
  
 NO NOTIFICATION HAS BEEN PROVIDED FOR THE MEZZANINE OR
 FOR THE CORRIDOR EAST OF APPLIANCE B1-1 OR NORTH OFFICE
 ENTRANCE NEAR PULL STATION M6.
  
 DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW