| Plan Review Notes For Permit 11050086 |
| Permit Number |
11050086 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-20 11:15:48 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE THE DESIGN PRESSURES FOR GARAGE DOOR TO | | | REFLECT EXPOSURE "C". SEC. R301.2.1.4.3 | | | | | | 2- SHEET A-7: A) PROVIDE ENGINEERING ANALYSIS FOR | | | STRUCTURAL GARAGE BUCK INSTALLATION. SHOW HOW THE 3/8" | | | RED HEAD ANCHORS SPACED AT 36"O.C WILL RESIST THE | | | REVISED GARAGE DOOR DESIGN PRESSURES FOR EXPOSURE "C". | | | SEE ITEM #1 ABOVE. ALSO, SEE GARAGE DOOR PRODUCT | | | APPROVAL FOR STRUCTURAL BUCK SPECIFICATIONS. SEC. | | | 106.1.2 OF CITY AMENDMENTS TO VERIFY COMPLIANCE WITH | | | SEC. R301.2.1.4.3. | | | | | | B) SPECIFY ATTIC VENTILATION SIZE AND LOCATION/SPACING | | | ON TYPICAL WALL SECTION. SEC. R806. | | | | | | 3- SHEET A-9: SPECIFY CONNECTORS FOR ALL TRUSSES. | | | TRUSSES MARKED WITH RED CIRCLES ARE MISSING THE | | | CONNECTOR SPECIFICATIONS. SEC. 106.1.2 CITY AMENDMENTS | | | TO FBC. | | | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVED IN WRITING | | | (NOT SIGNING & SEALING) ALL PRODUCT APPROVALS. SEC. | | | 106.3.3 CITY AMENDMENTS TO FBC. |
|