| 2011-05-04 09:17:07 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ENGINEER TO PROVIDE THE CALCULATED RAS 117 |
| | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON |
| | LAST PAGE OF NOA 10-1230.02 SUBMITTED. |
| | |
| | 2- FASTENER SPACING CAN'T BE LESS THAN 4"O.C. SEE SEC. |
| | 8.1 OF RAS 117 CALCULATIONS. ENGINEER SPECIFIED 3"O.C. |
| | FASTENER SPACING ON SECTION D FORM AND THE FLAT ROOF |
| | INFORMATION FORM SUBMITTED. REVISE AS REQUIRED. PLEASE |
| | DON'T USE THE PALM BEACH COUNTY FORMS. THOSE FORMS ARE |
| | NO PART OF THE CITY REQUIREMENTS FOR ROOFING PERMITS. |
| | PROVIDE REQUIRED INFORMATION ON SEPARATE SHEETS SIGNED |
| | AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE. |
| | |
| | 3- FASTENER SPACING SHALL BE ROUNDED DOWN TO THE NEXT |
| | WHOLE NUMBER NOT ROUNDED UP. SEE SEC. 10.4.5 OF RAS |
| | 117. IT LOOKS LIKE ENGINEER ROUNDED UP THE FASTENER |
| | SPACING FOR CORNER AREAS TO HAVE 2 ROWS IN THE CENTER |
| | OF THE SHEET. SEE SECTION D AND FLAT ROOF INFORMATION |
| | FORM SUBMITTED. REVISE AS REQUIRED. PLEASE DON'T USE |
| | PALM BEACH COUNTY FORMS. |
| | |
| | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR THE POLYFOAM TO BE USED. NONE WAS |
| | SUBMITTED AT THIS TIME. PLEASE VISIT THE MIAMI-DADE |
| | WEBSITE TO DOWNLOAD CURRENT NOA. |
| | |