| 2011-06-23 12:52:53 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE PROVIDE INFORMATION AS TO HOW YOU HAVE | | | DETERMINED THAT THE BOTTOM SUBSTRATE IS CONCRETE. CBS | | | HOMES ARE TYPICALLY CONCRETE TOP SUBSTRATE, BLOCK ON | | | THE BOTTOM. PLEASE EITHER REVISE BOTTOM CONNECTION FOR | | | BLOCK SUBSTRATE OR PROVIDE INFORMATION AS TO HOW A | | | CONCRETE SUBSTRATE (FORMED AND POURED CONCRETE, NOT | | | FILLED CELLS) HAS BEEN DETERMINED. | | | | | | 2. THE SHUTTER CONNECTION MOUNTING TYPE IS TO CORRELATE | | | WITH THE ANCHOR SCHEDULES (FOR INSTANCE, C1 - C5), SEE | | | PP 9-10 OF THE NOA. PLEASE REVISE AS CONNECTION TYPES | | | ARE NOT CLEAR. AN ATTEMPT WAS MADE TO PASS WITH | | | REDLINES, BUT OPENING 3 STATES THAT THE SHUTTER | | | CONNECTION MOUNTING TYPE IS "WALL/CEILING." WALL ON THE | | | TOP, CEILING CONNECTION ON THE BOTTOM? AS PROPOSED | | | INSTALLATION IS NOT CLEAR, IT WAS IMPOSSIBLE TO REDLINE | | | THE ANCHOR SPACING. | | | | | | |
|