| 2011-08-24 12:56:34 | PASS PROVISO | | | PROVIDE A LETTER FROM THE ENGINEER ON FLOOR SUPPORT | | | DETAIL # H-900 PAGE GH-2 | | | WHAT TYPE OF ANCHORING DEVICE IS BEING USED. | | | PROVIDE PRODUCT APPROVALS FOR THE LOUVERS,PER SECTION | | | 106.3.3 2007 FBC | | | SUPPLY FANS OVER 2000 CFM REQUIRE FAN SHUTDOWN PER | | | SECTION 606.2.1. | | | REFER TO SECTION 606.4.1 SUPERVISION. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|