| 2011-05-18 15:32:45 | 1009 BANYAN BOULEVARD |
| | PERMIT NUMBER 11050023 |
| | 'CONSTRUCTION OF A NEW ELECTRICAL / GENERATOR BUILDING |
| | AND ASSOCIATED FUEL TANKS" |
| | |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS |
| | OFTEN AS NECESSARY. |
| | |
| | 3. FIRE AND PARAMEDICAL ACCESS IS TO BE MAINTAINED TO |
| | THE CONSTRUCTION SITE. |
| | |
| | 4. ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY WITH |
| | NFPA 51B. CUTTING AND WELDING OPERATIONS SHALL NOT |
| | OCCUR IN FLAMMABLE GAS LOCATIONS AND A MINIMUM OF AT |
| | LEAST 35 FEET CLEARANCE IS REQUIRED TO ANY COMBUSTIBLE |
| | MATERIALS. |
| | |
| | 5. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FUEL |
| | TANKS AND GENERATORS. |
| | |
| | 7. ALL EMERGENCY SHUT-OFFS ARE TO BE PROPERLY |
| | IDENTIFIED WITH SIGNAGE INDICATING WHAT SYSTEM OR |
| | DEVICE IT SHUTS OFF. |
| | |
| | 8. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" |
| | HIGH AND AT LEAST 1" WIDE NUMBERS ARE TO BE PROVIDED. |
| | |
| | 9. A KNOX-BOX WILL BE REQUIRED. A KNOX-BOX CAN BE |
| | ORDERED AT WWW.KNOX-BOX.COM. |
| | |
| | 10. DUE TO THE EQUIPMENT CONTAINED IN THE BUILDING, THE |
| | BUILDING NEEDS TO BE PROPERLY LABELED. |
| | |
| | 11. ALL FIRE DAMPERS ARE TO BE TESTED TO ENSURE PROPER |
| | OPERATION AFTER INSTALLATION. |
| | |
| | 12. PLEASE PROVIDE MORE DETAILS ON ACOUSTIC BLANKETS |
| | PLANNED BETWEEN THE TRUSSES. (FLAME SPREAD AND SMOKE |
| | DEVELOPMENT) |
| | |
| | 13. DIESEL FUEL STORAGE TANKS AND THEIR APPURTENANCES |
| | SHALL COMPLY WITH NFPA 30. |
| | |
| | 14. PLEASE INDICATE ALL WARNING SIGNS, LABELS, AND |
| | LOCATIONS OF THE NFPA 704 DIAMONDS FOR THE FUEL STORAGE |
| | TANKS. |
| | |
| | 15. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM-200 |
| | SYSTEM PLANNED FOR THE TRANSFORMER ROOM. |
| | |
| | 16. GENERATORS TO COMPLY WITH NFPA 37 AND NFPA 110. |
| | |
| | 17. MORE DETAILS NEEDED ON FIRE ALARM RISER SHOWN ON |
| | PAGE E-31. |
| | |
| | 18. PROPER CLEARANCES ARE TO BE PROVIDED TO ELECTRICAL |
| | EQUIPMENT AND PANELS PER NFPA 70, THE NATIONAL |
| | ELECTRICAL CODE. |
| | |
| | 19. ALL TEMPORARY ELECTRICAL FEEDS AND EQUIPMENT SHALL |
| | BE PROPERLY SAFEGUARDED TO PREVENT INJURIES OR FIRES. |
| | |
| | 20. APPROPRIATE SIGNAGE WILL BE NECESSARY TO PREVENT |
| | STORAGE IN EXHAUST AND SUPPLY AIR AREAS. |
| | |
| | 21. ALL FIRE WALLS ARE TO BE PROPERLY LABELED PER THE |
| | FLORIDA BUILDING AND FLORIDA FIRE PREVENTION CODE. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |
| | |
| | |
| | |