Plan Review Notes For Permit 11050023
Permit Number 11050023
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-05-18 15:32:451009 BANYAN BOULEVARD
 PERMIT NUMBER 11050023
 'CONSTRUCTION OF A NEW ELECTRICAL / GENERATOR BUILDING
 AND ASSOCIATED FUEL TANKS"
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS
 OFTEN AS NECESSARY.
  
 3. FIRE AND PARAMEDICAL ACCESS IS TO BE MAINTAINED TO
 THE CONSTRUCTION SITE.
  
 4. ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY WITH
 NFPA 51B. CUTTING AND WELDING OPERATIONS SHALL NOT
 OCCUR IN FLAMMABLE GAS LOCATIONS AND A MINIMUM OF AT
 LEAST 35 FEET CLEARANCE IS REQUIRED TO ANY COMBUSTIBLE
 MATERIALS.
  
 5. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FUEL
 TANKS AND GENERATORS.
  
 7. ALL EMERGENCY SHUT-OFFS ARE TO BE PROPERLY
 IDENTIFIED WITH SIGNAGE INDICATING WHAT SYSTEM OR
 DEVICE IT SHUTS OFF.
  
 8. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE TO BE PROVIDED.
  
 9. A KNOX-BOX WILL BE REQUIRED. A KNOX-BOX CAN BE
 ORDERED AT WWW.KNOX-BOX.COM.
  
 10. DUE TO THE EQUIPMENT CONTAINED IN THE BUILDING, THE
 BUILDING NEEDS TO BE PROPERLY LABELED.
  
 11. ALL FIRE DAMPERS ARE TO BE TESTED TO ENSURE PROPER
 OPERATION AFTER INSTALLATION.
  
 12. PLEASE PROVIDE MORE DETAILS ON ACOUSTIC BLANKETS
 PLANNED BETWEEN THE TRUSSES. (FLAME SPREAD AND SMOKE
 DEVELOPMENT)
  
 13. DIESEL FUEL STORAGE TANKS AND THEIR APPURTENANCES
 SHALL COMPLY WITH NFPA 30.
  
 14. PLEASE INDICATE ALL WARNING SIGNS, LABELS, AND
 LOCATIONS OF THE NFPA 704 DIAMONDS FOR THE FUEL STORAGE
 TANKS.
  
 15. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM-200
 SYSTEM PLANNED FOR THE TRANSFORMER ROOM.
  
 16. GENERATORS TO COMPLY WITH NFPA 37 AND NFPA 110.
  
 17. MORE DETAILS NEEDED ON FIRE ALARM RISER SHOWN ON
 PAGE E-31.
  
 18. PROPER CLEARANCES ARE TO BE PROVIDED TO ELECTRICAL
 EQUIPMENT AND PANELS PER NFPA 70, THE NATIONAL
 ELECTRICAL CODE.
  
 19. ALL TEMPORARY ELECTRICAL FEEDS AND EQUIPMENT SHALL
 BE PROPERLY SAFEGUARDED TO PREVENT INJURIES OR FIRES.
  
 20. APPROPRIATE SIGNAGE WILL BE NECESSARY TO PREVENT
 STORAGE IN EXHAUST AND SUPPLY AIR AREAS.
  
 21. ALL FIRE WALLS ARE TO BE PROPERLY LABELED PER THE
 FLORIDA BUILDING AND FLORIDA FIRE PREVENTION CODE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  
  