| Plan Review Notes For Permit 11050023 |
| Permit Number |
11050023 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-05-27 16:18:11 | GE4: | | | PROVIDE NOTES ON THE PLAN OR REFERENCE THE | | | SPECIFICATIONS FOR THE REQUIRED SAFETY WARNINGS AT | | | ENTRANCES ETC. NEC 110.31 | | | PROVIDE NOTES ON THE PLAN OR REFERENCE THE | | | SPECIFICATIONS FOR THE REQUIRED FIELD MARKINGS FOR | | | FLASH PROTECTION. NEC 110.16 | | | E4: | | | MINIMUM ELECTRIC DUCT SEPARATION IS 7.5 INCHES. NEC | | | 310.60 | | | 15S-2: | | | CONTAINMENT CURB SHOULD BE OF SUFFICIENT HEIGHT TO | | | CONFINE THE OIL FROM THE LARGEST TRANSFORMER WITHIN THE | | | VAULT OR NO LESS THAN 4 INCHES IN HEIGHT. NEC 450.43(B) | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|