Plan Review Notes
Plan Review Notes For Permit 11050013
Permit Number 11050013
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-05-03 13:58:104233 UP THE GROVE LANE
 PERMIT #11050013
 MASTER #10120325
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE INSPECTORS TEST CONNECTION FOR MEANS OF TESTING
 WATERFLOW SWITCH.
  
 SHOP DRAWINGS INDICATE A HYDRAULICALLY REMOTE AREA OF
 1500 SQUARE FEET WHICH IS CONSISTENT WITH ENGINEER OF
 RECORD CONSTRUCTION DRAWINGS; HOWEVER, THE ACTUAL AREA
 CALCULATED APPEARS TO BE ROUGHLY 1250 SQUARE FEET. TO
 DEVIATE FROM THE CONSTRUCTION DRAWINGS AND USE THE AREA
 REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS, THE
 ENGINEER OF RECORD MUST PROVIDE DOCUMENTATION TO THE
 AHJ THAT THIS ALTERNATE DESIGN IS ACCEPTABLE.
  
 PROVIDE HYDRAULIC CALCULATIONS STARTING AT THE REMOTE
 END OF THE BRANCH LINE (DOWNSTREAM OF HYDRAULIC NODE
 1).
  
 INDICATE THE RESPONSIBLE PARTY FOR THE FIRE DEPARTMENT
 CONNECTION AND BACKFLOW PREVENTER. LOCKING KNOX CAPS
 ARE REQUIRED ON THE FIRE DEPARTMENT CONNECTION AND THE
 BACKFLOW PREVENTER REQUIRES TAMPER SWITCHES AND A CHAIN
 WITH LOCK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  