| Notes |
| Date |
Text |
| 2011-05-03 13:58:10 | 4233 UP THE GROVE LANE | | | PERMIT #11050013 | | | MASTER #10120325 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE INSPECTORS TEST CONNECTION FOR MEANS OF TESTING | | | WATERFLOW SWITCH. | | | | | | SHOP DRAWINGS INDICATE A HYDRAULICALLY REMOTE AREA OF | | | 1500 SQUARE FEET WHICH IS CONSISTENT WITH ENGINEER OF | | | RECORD CONSTRUCTION DRAWINGS; HOWEVER, THE ACTUAL AREA | | | CALCULATED APPEARS TO BE ROUGHLY 1250 SQUARE FEET. TO | | | DEVIATE FROM THE CONSTRUCTION DRAWINGS AND USE THE AREA | | | REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS, THE | | | ENGINEER OF RECORD MUST PROVIDE DOCUMENTATION TO THE | | | AHJ THAT THIS ALTERNATE DESIGN IS ACCEPTABLE. | | | | | | PROVIDE HYDRAULIC CALCULATIONS STARTING AT THE REMOTE | | | END OF THE BRANCH LINE (DOWNSTREAM OF HYDRAULIC NODE | | | 1). | | | | | | INDICATE THE RESPONSIBLE PARTY FOR THE FIRE DEPARTMENT | | | CONNECTION AND BACKFLOW PREVENTER. LOCKING KNOX CAPS | | | ARE REQUIRED ON THE FIRE DEPARTMENT CONNECTION AND THE | | | BACKFLOW PREVENTER REQUIRES TAMPER SWITCHES AND A CHAIN | | | WITH LOCK. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|