2011-05-05 07:39:202007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS SPECIFYING THE
 LOCATION AND SIZES OF THE NEW SUPPLY AND RETURN DUCTS,
 TRANSFER DUCTS, TRANSFER GRILLS, ETC. SPECIFY THE GRILL
 SIZES, LOCATIONS AND CFMS ON THE PLANS. CITY AMENDMENTS
 106.3.5.4
  
 2) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE HVAC
 CONTRACTOR OR TITLE BLOCK, SIGNATURE AND SEALED OF THE
 DESIGN PROFESSIONAL IS REQUIRED ON THE MECHANICAL
 PLANS. CITY AMENDMENTS 106.1.3
  
 3) SUBMIT ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS TO VERIFY THAT THE EXISTING HVAC SYSTEM
 WILL BE ADEQUATE FOR THE ADDITIONAL LOAD. CITY
 AMENDMENTS 106.3.5.4
  