| 2011-05-05 07:39:20 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS SPECIFYING THE | | | LOCATION AND SIZES OF THE NEW SUPPLY AND RETURN DUCTS, | | | TRANSFER DUCTS, TRANSFER GRILLS, ETC. SPECIFY THE GRILL | | | SIZES, LOCATIONS AND CFMS ON THE PLANS. CITY AMENDMENTS | | | 106.3.5.4 | | | | | | 2) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE HVAC | | | CONTRACTOR OR TITLE BLOCK, SIGNATURE AND SEALED OF THE | | | DESIGN PROFESSIONAL IS REQUIRED ON THE MECHANICAL | | | PLANS. CITY AMENDMENTS 106.1.3 | | | | | | 3) SUBMIT ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS TO VERIFY THAT THE EXISTING HVAC SYSTEM | | | WILL BE ADEQUATE FOR THE ADDITIONAL LOAD. CITY | | | AMENDMENTS 106.3.5.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|