2011-04-29 14:14:09ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE.
 PLEASE PROVIDE THE FOLLOWING.
  
 PROVIDE TYPICAL PANEL SCHEDULE WITH BREAKER SIZES
 INCLUDING MAIN DISCONNECT.
 SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING
 CAPACITY IS SUFFICIENT.
 SHOW AFCI PROTECTED CIRCUITS
 SHOW REQUIRED 20 AMP BRANCH CIRCUITS
 SHOW RANGE AND WATER HEATER
 SHOW HEAT AND AIR CONDITIONING
 PROVIDE INTERCONNECTED SMOKE DETECTORS AND CARBON
 MONOXIDE DETECTOR
 LOCATE ELECTRIC PANEL ON PLAN
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE
 NEW RECEPTACLES MUST BE TAMPER RESISTANT
 VERIFY WORK VALUE WITH COPY OF CONTRACT.
 RESUBMIT THE SECOND FLOOR PLAN. COPY IS OF POOR QUALITY
 AND NOT REPRODUCIBLE FOR IMAGING PURPOSES.
  