| Plan Review Notes For Permit 11040749 |
| Permit Number |
11040749 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-29 14:14:09 | ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE. | | | PLEASE PROVIDE THE FOLLOWING. | | | | | | PROVIDE TYPICAL PANEL SCHEDULE WITH BREAKER SIZES | | | INCLUDING MAIN DISCONNECT. | | | SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING | | | CAPACITY IS SUFFICIENT. | | | SHOW AFCI PROTECTED CIRCUITS | | | SHOW REQUIRED 20 AMP BRANCH CIRCUITS | | | SHOW RANGE AND WATER HEATER | | | SHOW HEAT AND AIR CONDITIONING | | | PROVIDE INTERCONNECTED SMOKE DETECTORS AND CARBON | | | MONOXIDE DETECTOR | | | LOCATE ELECTRIC PANEL ON PLAN | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT | | | VERIFY WORK VALUE WITH COPY OF CONTRACT. | | | RESUBMIT THE SECOND FLOOR PLAN. COPY IS OF POOR QUALITY | | | AND NOT REPRODUCIBLE FOR IMAGING PURPOSES. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|