| Plan Review Notes For Permit 11040742 |
| Permit Number |
11040742 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-07-12 08:09:30 | 410 EVERNIA STREET, SUITE #108 | | | PERMIT #11040742 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE TACTILE SIGNAGE AT EXIT DOORS. | | | | | | VISUAL FIRE ALARM NOTIFICATION APPLIANCES ARE REQUIRED | | | IN ALL PUBLIC AREAS SUCH AS RESTROOMS. | | | | | | THE FIRE SPRINKLER SYSTEM WILL BE REQUIRED TO BE | | | CONVERTED TO AN NFPA 13 SYSTEM WITH SPRINKLERS IN ALL | | | SPACES, INCLUDING SMALL CLOSESTS, RESTROOMS ETC. THE | | | RESIDENTIAL SPRINKLERS WILL NEED TO BE REPLACED WITH | | | COMMERCIAL QUICK RESPONSE SPRINKLERS. NOTE: PENDENT | | | SPRINKLERS MAY NEED TO REPLACE SIDEWALL SPRINKLERS TO | | | COMPLY WITH CEILING/SOFFIT OBSTRUCTIONS. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|