Plan Review Notes
Plan Review Notes For Permit 11040742
Permit Number 11040742
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2011-07-12 08:09:30410 EVERNIA STREET, SUITE #108
 PERMIT #11040742
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 VISUAL FIRE ALARM NOTIFICATION APPLIANCES ARE REQUIRED
 IN ALL PUBLIC AREAS SUCH AS RESTROOMS.
  
 THE FIRE SPRINKLER SYSTEM WILL BE REQUIRED TO BE
 CONVERTED TO AN NFPA 13 SYSTEM WITH SPRINKLERS IN ALL
 SPACES, INCLUDING SMALL CLOSESTS, RESTROOMS ETC. THE
 RESIDENTIAL SPRINKLERS WILL NEED TO BE REPLACED WITH
 COMMERCIAL QUICK RESPONSE SPRINKLERS. NOTE: PENDENT
 SPRINKLERS MAY NEED TO REPLACE SIDEWALL SPRINKLERS TO
 COMPLY WITH CEILING/SOFFIT OBSTRUCTIONS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW