2011-05-03 17:07:22410 EVERNIA STREET, SUITE #108
 PERMIT #11040742
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 THE OCCUPANT LOAD SHOULD BE CALCULATED USING 15 SQUARE
 FEET PER PERSON AS DISPLAYED IN TABLE 7.3.1.2 OF NFPA
 101 (WITH FLORIDA AMENDMENTS). IF THE OCCUPANT LOAD
 RESULTS IN FEWER THAN 50 PERSONS, THE OCCUPANCY TYPE
 CAN BE DEEMED AS MERCANTILE AND NOT SMALL ASSEMBLY.
 (769 SQ.FT./15 SQ.FT. = 52 PERSONS)
  
 EXIT DOORS ARE REQUIRED TO SWING OUTWARD WHEN THE
 OCCUPANT LOAD EXCEEDS 49 PERSONS.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 EMERGENCY LIGHTING IS REQUIRED FOR ASSEMBLY
 OCCUPANCIES.
  
 INDICATE THE LOCATIONS OF FIRE ALARM DEVICES ON THE
 LIFE SAFETY PLAN. VISUAL NOTIFICATION APPLIANCES ARE
 REQUIRED IN ALL PUBLIC AREAS SUCH AS RESTROOMS.
  
 THE FIRE SPRINKLER SYSTEM WILL BE REQUIRED TO BE
 CONVERTED TO AN NFPA 13 SYSTEM WITH SPRINKLERS IN ALL
 SPACES, INCLUDING SMALL CLOSESTS, RESTROOMS ETC. THE
 RESIDENTIAL SPRINKLERS WILL NEED TO BE REPLACED WITH
 COMMERCIAL QUICK RESPONSE SPRINKLERS. NOTE: PENDENT
 SPRINKLERS MAY NEED TO REPLACE SIDEWALL SPRINKLERS TO
 COMPLY WITH CEILING/SOFFIT OBSTRUCTIONS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  