| 2011-05-09 16:00:32 | BUILDING PLAN REVIEW |
| | PERMIT: 11040742 |
| | ADD: 410 EVERNIA # 108 |
| | CONT: TBD |
| | TEL: (561)651-1011 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET: |
| | |
| | 1A) THE PLANS LIST THE EXISTING OCCUPANCY AS A WORK |
| | LIVE UNIT. PLEASE REVIEW SECTION 302- 313 OF THTE 2007/ |
| | 09 FBC-B. SECTION 302.1 2007/09 FBC-B, WHERE A |
| | STRUCTURE IS PROPOSED FOR A PURPOSE THAT IS NOT |
| | SPECIFICALLY PROVIDED FOR IN THIS CODE, SUCH STRUCTURE |
| | SHALL BE CLASSIFIED IN THE GROUP THAT THE OCCUPANCY |
| | MOST NEARLY RESEMBLES, ACCORDING TO THE FIRE SAFETY AND |
| | RELATIVE HAZARD INVOLVED. THE ORIGINAL HIGHRISE PERMIT |
| | LISTED THESE UNITS AS RESIDENTIAL UNITS WITH A |
| | MEZZANINE. PERMIT SET OF PLANS 03/22/04 |
| | PLEASE CORRECT THE OCCUPANCY TYPE FOR THE MEZZANINE |
| | LEVEL. |
| | |
| | 1B) THE SECOND ISSUE WITH THE COVER SHEET IS THE AMOUNT |
| | OF OCCUPANTS FOR THIS TENANTACY. THE OCCUPANT LOAD FOR |
| | THE FIRST FLOOR WILL BE 30 SQ FT PER PERSON 2007 FBC-B |
| | TABLE 1004.1.1. PLEASE PROVIDE THE OCCUPANCY TYPE FOR |
| | THE MEZZANINE LEVEL FOR AN ACCURATE OCCUPANT LOAD |
| | COUNT. DEPENDING ON THE MEZANINE OCCUPANCY MORE |
| | COMMENTS MAY BE FORTH COMING. |
| | |
| | 1C) THE LEVEL OF ALTERATION IS NO LONGER A LEVEL II BUT |
| | A CHANGE OF OCCUPANCY FOUND IN CHAPTER 9 OF THE 2007/ |
| | 09 EXISTING BUILDING CODE. |
| | 901.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| | NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY. |
| | |
| | 1D) THE COVER SHEET LIFE SAFETY SHEET INDICATES EXITING |
| | THROUGH THE KITCHEN AREA. REVIEW 2007 FBC-B 1014.2 (2) |
| | EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, |
| | CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | |
| | 1E) THE REAR ENTRY DOOR VERSES NEW CABINTRY LESS THAN |
| | 18" FROM THE DOOR TO COUNTER TOP. 2007/09 FBC-B SECTION |
| | 1008.1.8.8 WOULD REQUIRE A MINIMUM OF 18 INCHES. |
| | |
| | 1F) PLANS FAIL TO PROVIDE ANY DETAILED INFORMATION AS |
| | FAR AS ACCESSIBILITY/ 2007 /09 FBC-B: |
| | 11-5.2 COUNTERS & BARS |
| | 11-5.3 ACCESS AISLES |
| | 11-5.4 DINING AREAS |
| | 11-5.6 CONDIMENT AREAS. |
| | |