| Plan Review Notes For Permit 11040709 |
| Permit Number |
11040709 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-29 15:34:31 | REVISON REQUIRES SOME ADDITIONAL INFORMATION. PLEASE | | | HAVE ELECTRICAL CONTRACTOR UPDATE THE PLAN WITH AS | | | BUILT CONDITIONS. | | | | | | AS EXAMPLE THE REQUIRED SMOKE AND CARBON MONIXODE | | | DECTORS ARE NOT CLEARLY SHOWN. THE ELECTRICAL RISER | | | SHOWS TWO PANELS WITH THE SAME ( "A") DESIGNATION. WIRE | | | SIZES ON THE PANEL SCHEDULES FOR THE WALL OVEN AND | | | KITCHEN ARE INCORRECT. ETC. | | | | | | ALL REVISIONS/CHANGES SHOULD BE CLOUDED AND PROPERLY | | | REFERANCED. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|