| Plan Review Notes For Permit 11040655 |
| Permit Number |
11040655 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-05-03 14:27:42 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. ANCHOR SPACING DOES NOT COMPLY WITH PRODUCT APPROVAL | | | FOR SEVERAL OPENINGS. FOR INSTANCE, SEE OPENING 7. ALL | | | OTHER 83" SPAN OPENINGS WITH SAME CONDITIONS HAVE 10" | | | SPECIFIED, BUT 12" IS PROPOSED FOR OPENING #7. 10" IS | | | PROPOSED FOR CONNECTION TYPE D, BUT 8" IS REQUIRED FOR | | | OPENINGS 2, 5, 6, 7. CONNECTION TYPE L FOR A 103" SPAN, | | | TAPCONS REQUIRES 5" ANCHOR SPACING, 10" PROPOSED. | | | | | | THESE ARE EXAMPLES. PLEASE CHECK ALL. RESUBMITTAL MAY | | | BE DONE VIA EMAIL FOR THIS PROJECT ONLY. PLEASE HAVE | | | THE QUALIFIER REVIEW PRIOR TO RESUBMITTAL. | | | | | | |
|